Hydro Smart 115 Manuel De Montage

Page de 44
Installation 
20
Page
 
 
Do  not  use  this  water  heater  if  any  part  has  been  submersed  under  water. 
Immediately call a licensed professional to inspect the water heater to replace 
any damaged parts. 
 
Do not reverse the hot outlet and cold inlet connections to the water heater.  
This will not properly activate the water heater. 
WATER CONNECTIONS 
 
 
 
 
 
 
 
All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for 
potable water systems.  
1. 
A manual shut off valve must be installed on the cold water inlet to the water heater between 
the main water supply line and the water heater.  
2. 
In  addition,  a  manual  shut  off  valve  is  also 
recommended  on  the  hot  water  outlet  of  the 
unit.  If  the  water  heater  is  installed  within,  or 
subjected  to,  a  closed  loop  water  system,  a 
thermal expansion tank must be installed.  
3. 
Before  installing  the  water  heater,  flush  the 
water  line  to  remove  all  debris,  and  after 
installation is complete, purge the air from the 
line.  Failure to do so may cause damage to the 
heater.  
4. 
There  is  a  wire  within  the  cold  inlet  to  trap 
debris from entering your heater. This will need 
to be cleaned periodically to maintain optimum 
flow.  
‐Pressure relief valve‐ 
The water heater has a high‐temperature shut off switch built in as a standard safety feature (called a 
Hi‐Limit switch) therefore a “pressure only” relief valve is required. 
  This unit does not come with an approved pressure relief valve.  
  An approved pressure relief valve must be installed on the hot water outlet.  
  The pressure relief valve must conform to ANSI Z21.22 or CAN 1‐4.4 and installation must follow    
local code.  
  The discharge capacity must be at least 140,000 BTU/h.  
  The pressure relief valve needs to be rated for a maximum of 150 psi. 
  The discharge piping for the pressure relief valve must be directed so that the hot water cannot 
splash on anyone or on nearby equipment.  
  Attach the discharge tube to the pressure relief valve and run the end of the tube to within 6" 
from  the  floor.  This  discharge  tube  must  allow  free  and  complete  drainage  without  any 
restrictions. 
  If the pressure relief valve installed on the water heater discharges periodically, this may be due 
to a defective thermal expansion tank or defective pressure relief valve.  
  The pressure relief valve must be manually operated periodically to check for correct operation. 
  No valve must be placed between the relief valve and the water heater. 
Pressure  
Relief Valve 
Hot  
outlet 
Cold 
inlet 
Gas 
inlet
As Close as
Possible
CAUTION