Site Preparation
Liebert
®
 MC
6
2.0
S
ITE
 P
REPARATION
2.1
Site Considerations
• Condensers should be installed in a location offering maximum security and access for 
maintenance.
• Avoid ground-level sites with public access and areas prone to heavy snow or ice accumulations. 
• To ensure adequate air supply, Emerson
®
 recommends that condensers be installed in an area 
with clean air, away from loose dirt and foreign matter that might clog the coil. In addition, 
condensers should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.
• For roof installation, mount the condenser on suitable curbs or other supports in accordance with 
local codes.
• Condensers must not be installed in a pit.
• Condensers must be installed on a level surface to ensure proper refrigerant flow.
• Use caution when installing condensers below the indoor unit. Condensers must not be installed 
more than 15ft. (4.6m) below the indoor unit. Condensers with Liebert Lee-Temp
 receivers must 
be installed at or above the level of the indoor units to maintain proper subcooling.
• Liebert Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. 
Contact Emerson Application Engineering Department for assistance with applications requiring 
remote mounting of receivers.
• Condensers must be installed in vertical airflow orientation to maintain the electrical box’s 
NEMA 3R rating.
2.2
Dimensions and Weights
Table 1
Condenser net weights, shipping weights, dimensions and volume, approximate
Model #
Number
of Fans
Condenser
Net Weight
lb (kg)
Domestic Packaging
Export Packaging
Packaged
Weight
lb (kg)
Dimensions
(LxWxH)
in. (cm)
Volume 
ft
3
 (m
3
)
Packaged
Weight
lb (kg)
Dimensions
(LxWxH)
in. (cm)
Volume
ft
3
 (m
3
)
MCS028
1
154 (70)
335 (152)
76x36x63
(193x91x160) 100 (2.8)
455 (206)
77x37x64
(196x94x163) 106 (3.0)
MCM040
1
231 (105)
410 (186)
76x36x63 
(193x91x160)
100 (2.8)
535 (243)
77x37x64
(196x94x163)
106 (3.0)
MCM080
2
441 (200)
750 (340)
136x36x63 
(345x91x160) 179 (5.0)
945 (429)
137x37x64
(348x94x163) 188 (5.3)
MCM120
3
672 (305)
1110 (503)
196x36x63 
(498x91x160) 257 (7.3) 1380 (626)
197x37x64
(413x66x142) 270 (7.7)
MCM160
4
860 (390)
1425 (646)
256x36x63 
(650x91x160)
336 (9.5) 1770 (803)
257x37x64
(653x94x163)
352 (10)
MCL055
1
344 (156)
525 (238)
76x36x63 
(193x91x160) 100 (2.8)
645 (293)
77x37x64
(196x94x163) 106 (3.0)
MCL110
2
602 (273)
910 (413)
136x36x63 
(345x91x160) 179 (5.0) 1110 (503)
137x37x64
(348x94x163) 188 (5.3)
MCL165
3
891 (404)
1330 (603)
196x36x63 
(498x91x160)
257 (7.3) 1600 (726)
197x37x64
(413x66x142)
270 (7.7)
MCL220
4
1186 (538)
1755 (796)
256x36x63 
(650x91x160) 336 (9.5) 2095 (950)
257x37x64
(653x94x163) 352 (10)
Net and packaged weights will increase with factory options: legs taller than 18", coated coils and seismic options. 
Field-installed receivers also add to net weights. Consult factory for additional information.
Table 2
Condenser net weight addition—taller legs
Leg Height
In. (mm)
Additional Weight by Condenser Model, lb. (kg)
MCS028
MCM040
MCM080
MCM120
MCM160
MCL055
MCL110
MCL165
MCL220
36 (914)
120
120
139
242
236
127
148
222
242
48 (1219)
151
151
171
304
283
159
179
269
289
60 (1524)
183
183
202
367
330
190
210
316
336