Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW Manuel D’Utilisation

Page de 68
Site Preparation
Liebert
®
 MC
8
Figure 4
Condenser planning dimensions—MCM040, MCM080, MCM160 with/without Liebert Lee-Temp
Liebert
Model #
No.
Fans
A
In. (mm)
B
In. (mm)
C
In. (mm)
D
In. (mm)
E
In. (mm)
Leg 
Height
F * In 
(mm)
G
H
MCM040 
1
57-3/16 (1453)
48 (1219) 
46-5/16 (1177)
18 (457) 31-5/8 (803) 39-5/8 (1006
MCM080
2
105-1/4 (2674)
96-1/16 (2440) 94-7/16 (2398)
36 (914) 49-5/8 (1260) 57-5/8 (1464)
MCM160
4
202-7/16 (5142) 113-1/2 (2883) 192-1/4 (4883) 94-7/16 (2398) 96-3/16 (2444)
48 (1219) 61-5/8 (1565) 69-5/8 (1768)
Source: DPN002172, Rev. 3; DPN002189, Rev. 4
60 (1524) 73-5/8 (1870) 81-5/8 (2073)
* 18" legs standard for all models. Cross-bracing required for legs longer than 18". Number varies according to model and options.
See Tables 1 and 2 for weights, including added weight for legs of various lengths. Source: DPN002172, Rev. 3; and DPN002189, Rev. 4.
DPN002172, Rev 3
DPN002189, Rev. 4
  A
  B
  C
  F
  G
H
  D
E
46-5/16"
(1177mm)
44-3/8"
(1127mm)
Leg supplied for
each Liebert
Lee-Temp kit on
2- & 4-fan models
Electric Box End
39-5/16"
(999mm)
46"
(1168mm)
46"
(1168mm)
15-1/4"
387mm
15-1/4"
387mm
For dual
circuit only
46-1/4"
(1175mm)
46-1/4"
(1175mm)
Height to Top
of Fan Guard
Height to Top
of Fan Guard
Provided On
Four-Fan Models
Emerson recommends a clearance of
36" (915mm) on each side for proper
operation and component access.
Eyebolts for lifting
condenser provided
on four-fan models
  A
  B
  C
  F
  G
H
46-5/16"
(1177mm)
44-3/8"
(1127mm)
39-5/16"
(999mm)
One-Fan
Condenser
Electric Box End
ANCHOR PLAN
(One-Fan Condenser)
ANCHOR PLAN
For typical footprint 
dimensions, see Figure 2
See table 
below for 
dimensions 
F, G and H