8.15 Programmable settings 
 
8.15.1 Regulation settings 
 
 
 
Minimum 
setting 
Nominal 
setting 
Maximum 
setting 
 
 
 
 
 
Number of motor starts 
starts/day 
240 
720 
720 
Minimum stop time 1) sec 
30 
Stop between 2 compressor 
modules 
sec 2  2  5 
Start between 2 compressor 
modules 
sec 2  2  10 
Power recovery time 3) sec 
10 
10 
3600 
 
Delay at restarting after 
power recovery 3) 
sec 0  0 1200 
 
 
 
 
 
Minimum pressure 2) 
 
 
 
 
8 bar Pack 
bar(e) 
7.9 
8 bar Full-Feature 
bar(e) 
6.8 
7.7 
10 bar Pack 
bar(e) 
9.9 
10 bar Full-Feature 
bar(e) 
8.8 
9.7 
100 psi Pack 
bar(e) 
7.9 
100 psi Full-Feature 
bar(e) 
6.8 
7.7 
125 psi Pack 
bar(e) 
8.1 
125 psi Full-Feature 
bar(e) 
7.75 
8.8 
145 psi Pack 
bar(e) 
9.9 
145 psi Full-Feature 
bar(e) 
8.8 
9.7 
 
 
 
 
 
Maximum pressure 2) 
 
 
 
 
8 bar Pack 
bar(e) 
4.1 
8 bar Full-Feature 
bar(e) 
4.1 
7.8 
7.8 
10 bar Pack 
bar(e) 
4.1 
10 
10 
10 bar Full-Feature 
bar(e) 
4.1 
9.8 
9.8 
100 psi Pack 
bar(e) 
4.1 
100 psi Full-Feature 
bar(e) 
4.1 
7.8 
7.8 
125 psi Pack 
bar(e) 
4.1 
9.1 
9.1 
125 psi Full-Feature 
bar(e) 
4.1 
8.9 
8.9 
145 psi Pack 
bar(e) 
4.1 
10 
10 
145 psi Full-Feature 
bar(e) 
4.1 
9.8 
9.8 
 
 
 
 
 
For Full-Feature also 4) 
 
 
 
 
Dewpoint warning 
temperature 
°C 3 15 
40 
Delay at signal 5) sec  0 
10 
Delay at starting 6) sec 
255  255