ADT-LCD40 Series Annunciators
SW1 DIP Switch Settings
10
Document 50520    Rev D   7/25/00   P/N 50520:D
1.3
SW1 DIP Switch Settings
The Up position on DIP switch SW1 is the Off state.  Refer to “DIP 
Switch Settings Example” on page 11, for an explanation of DIP switch 
positions.  SW1 switch settings follow:
1 - On (Down) = Receive/Transmit, Off (up) = Receive Only.
Set switch 1 to Off (Up) position for all ADT-LCD40 Series Annun-
ciators except the last (or only) annunciator on the EIA-485 loop.  
Set switch to On (Down) position for the last or only annunciator on 
the EIA-485 loop to allow transmission of a supervision signal (and 
function switch depressions on the ADT-LCD40) back to the FACP.  
The last or only annunciator must be set for Receive/Transmit 
(switch 1 in the Down position).
A break (open circuit) in the power or EIA-485 connections creates 
an ADT-LCD40 Series Annunciator fault at the Unimode 200 panel.  
All annunciators before the break will continue to display informa-
tion (but the function switches on the ADT-LCD40 will no longer 
operate
).
2 - ADT-LCD40 Only (not used on the ADT-LCD40L)
     On (Down) = Key-switch enabled, Off (Up) = Key-switch disabled.
Switch 2 set to the On (Down) position enables key-switch 
operation.  The key-switch may now be used to enable the 
ADT-LCD40 membrane switches, allowing remote switch func-
tions, or lockout the switches, preventing remote switch functions
Switch 2 set to the Off (Up) position disables the key-switch 
operation.  Refer to “Switch Functions for ADT-LCD40 Only” on 
page 14, for key-switch function description.
3 - On (Down) = Piezo sounder enabled, Off (Up) = Piezo sounder 
      disabled.
CAUTION: Piezo sounder must not be disabled without prior 
approval of the Local Authority Having Jurisdiction (LAHJ).
4 through 8 = Future use.