ADT Security Services ADT-LCD40 Manuel D’Utilisation

Page de 36
ADT-LCD40 Series Annunciators
Typical Configuration
12
Document 50520    Rev D   7/25/00   P/N 50520:D
1.4
Typical Configuration
The ADT-LCD40 Series Annunciators mimic the Unimode 200 display, 
have full point-display capacity and require no programming.  The 
ADT-LCD40 offers multiple annunciator locations with the capability 
of remote Acknowledge, Signal Silence, Drill and Reset functions. 
Notes:
1. EIA-485: maximum of 6,000 feet (1,800 m) total cable length 
from FACP to annunciator and back to FACP for supervision 
(3,000 feet [900 m] maximum to last ADT-LCD40).  Circuit is 
power-limited.
2. Up to 32 ADT-LCD40 Series Annunciators may be used on the 
EIA-485 circuit.  The Unimode 200 can power a maximum of 
five annunciators.  If additional annunciators are connected, the  
FCPS-24F may be used to supply additional power.  Power 
supplies used for this purpose must have their negative terminals 
commoned together.
3. Between each ADT-LCD40 Series annunciator are four wires - a 
twisted shielded pair for data communications and a pair for 24 
VDC power.  The return circuit only requires two wires for data 
communication supervision, wired from the last or only annunci-
ator on the line.
Ac k
Sile nc e
Re s et
Dri ll
Hol d 2 se c.
F I R E   A L A R M   A N N U N C IA T O R
Ac k
Sile nc e
Re s et
Dri ll
Hol d 2 se c.
F I R E   A L A R M   A N N U N C IA T O R
Ac k
Sile nc e
Re s et
Dri ll
Hol d 2 se c.
F I R E   A L A R M   A N N U N C IA T O R
Figure 1-4: Typical Configuration
3,000 feet (900 m) to last device on loop
3,000 feet (900 m) back from last device on loop
Terminal Mode EIA-485 return (2 wires)
Terminal Mode EIA-485 (2 wires)
24 VDC (2 wires)