ADT Security Services ADT-LCD40 Manuel D’Utilisation

Page de 36
EIA-485 Shield Termination
EIA-485 Shield in Full Conduit
27
Document 50520    Rev D   7/25/00   P/N 50520:D
5.2
EIA-485 Shield in Full Conduit
The EIA-485 line allows the FACP to communicate with the 
ADT-LCD40 Series Annunciators.  The shield for the EIA-485 line 
must be connected to earth ground at the FACP (both exiting and 
entering the FACP) but must be left floating (no connection) at the 
annunciator if it is the first or only device on the EIA-485 line.  If a 
second annunciator is connected, the shield leaving the first annunciator 
must be floating.  The shield entering the second annunciator must be 
connected to the Earth Ground terminal (P2-7) on the second annuncia-
tor.  If additional annunciators are connected, the shield leaving each 
annunciator must be left floating and the shield entering the following 
unit must be connected to the Earth Ground terminal (P2-7) on the 
annunciator.
Caution! Do not allow the floating (no connection) end of the shield to 
contact the conduit.  The floating end should be insulated from earth 
ground.
Figure 5-2: EIA-485 In Conduit
ADT-LCD40 Series Box
ADT-LCD40 Series 
P1-2 (+)
EIA-485 (IN)
P1-4 (-)
EIA-485 (IN)
P2-7 Earth 
Ground (IN)
Connect the shield drain wire to the Earth 
Ground Terminal on the ADT-LCD40 Series 
Annunciator
Shield Drain Wire
Notes:
1) Power-limited 24 VDC power may be run in the same conduit as the EIA-485 wiring
2) Twisted, shielded wire is recommended for the EIA-485 communications loop
3) Each ADT-LCD40 Series electrical backbox is connected to earth ground via the conduit
4) Shield is connected to the FACP cabinet (earth ground) leaving and entering the FACP