Programming the Unimode 200
EIA-485 In Conduit
28
Document 50520    Rev D   7/25/00   P/N 50520:D
Section 6:          
Programming the Unimode 200
The Unimode 200 must be programmed to allow use of the 
ADT-LCD40 Series Annunciators.  In order to program the Unimode 
200, make certain the main circuit board 'Write Protect' switch (SW1) is 
in the down position and then press the ENTER key on the panel key-
pad.  After pressing ENTER, the screen shown below is displayed:
       1 = PROGRAMMING
     2=RD.STATUS 3=AC/BAT
To enter the Programming Mode, press '1'.  The display will read:
      KEY PASSWORD, ENTER
Enter the Level 1 password.  The following screen will appear:
     0=CLR 1=AUTO 2=POINT
     3=SYS 4=PWORD 5=LOAD
Press '3' to enter System Edit.  The system edit screen may appear as 
shown (note that previous programming may have altered some N or No 
designations to Y or Yes):
      V=N I=N A=N P=N C=N
      A/U=N L/P=N S=4 R=4
Use the left and right arrow keys to move to the L/P option.  Once at the 
L/P option, to enable the ADT-LCD40 Series Annunciator option, use 
the up and down arrow keys to scroll to the L (for ADT-LCD40 Series 
Annunciator) choice.  The ADT-LCD40 Series can now communicate 
with the Unimode 200.  
To leave Programming Mode, press the Backspace (left arrow) key 
repeatedly until Program Mode is exited.