 Geo Brick Drive User Manual 
Pinouts and Software Setup 
 117 
 
 
Note 
With  absolute  serial  encoders  (no  multi-turn  data),  the  power-on 
position format is set up for unsigned operation. 
 
 
Note 
The  upper  two  fields  in  Ixx95  are  the  only  relevant  ones.  Bits  0 
through 15 are reserved and should always be set to 0.  
 
Power-On Position scaling PLC example (for technique 2) 
M162->D:$00008B  
 
 
 
; #1 Actual position (Suggested M-Variable) 
 
Open PLC 1 clear 
I5111=100*8388608/I10 while(I5111>0) endw 
; 100 msec delay 
CMD“#1K“ 
 
 
 
 
; Make sure motor(s) killed 
I5111=100*8388608/I10 while(I5111>0) endw 
; 100 msec delay 
CMD“#1$*“ 
 
 
 
 
; Read un-scaled absolute position 
I5111=100*8388608/I10 while(I5111>0) endw 
; 100 msec delay 
M162=M162/32 
 
 
 
 
; Scale absolute position (shift right 5 bits) 
I5111=100*8388608/I10 while(I5111>0) endw 
; 100 msec delay 
Dis PLC 1 
 
 
 
 
; Run once on power-up or reset 
Close 
 
 
Note 
Some  serial  encoders  use  an  external  (not  from  the  Brick)  source  for 
power.  Make  sure  that  this  power  is  applied  prior  to  performing  an 
absolute read on power-up.