Delta Tau GEO BRICK DRIVE Manuel D’Utilisation

Page de 294
 Geo Brick Drive User Manual 
List of Changes and Updates 
 282 
LIST OF CHANGES AND UPDATES 
This is a list of significant changes and user related updates:  
 
AMPVER Command, December 2007 
 
 
Caution 
Failure to execute the AMPVER command on power-up for firmware 
1.943 and earlier can result in equipment damage. 
 
Geo Brick Drives, firmware version 1.943 and earlier, require a minimum delay of 500 milliseconds and 
the  issuing  of  AMPVER  command  on  power  up.  This  will  ensure  establishing  communication  between 
the amplifier processor and the PMAC, thus conveying amplifier faults and status properly. 
 
Example: 
OPEN PLC 1 CLEAR 
DIS PLCC 0..31  
; Disable all compiled PLCs 
DIS PLC 0 
 
; Disable foreground PLC 
DIS PLC 2..31   
; Disable background PLCs 
I5111=500*8388608/I10  ; 500 ms delay using C.S1 countdown timer 
WHILE(I5111>0)  
;  
END WHILE 
 
;  
 
CMD"AMPVER" 
 
;  
I5111=20*8388608/I10  ; 20 ms delay using C.S1 countdown timer. 
WHILE(I5111>0)  
; This provides enough time for the drive  
  
END WHILE 
 
; to process the ampver command.  
ENAPLC 2..31 
 
; Re-enable background PLCs 
ENAPLC 0 
 
; Re-enable foreground PLC 
ENA PLCC 0..31  
; Re-enable all compiled PLCs 
DISABLE PLC 1   
; Disable PLC 1, run only once on power up or reset 
CLOSE 
 
Quick Verification:  
The TYPE command, issued from a terminal window should return TURBO2, AMP, X4 
 
This is the desired response. A response of TURBO2, X4 is not appropriate (the Drive should not be used 
in this case) and it implies that the PLC has not executed properly (i.e., I5 setting) and/or the AMPVER 
command has not been issued, or executed properly. 
 
 
Note 
Geo  Brick  Drives,  with  firmware  version  1.944  and  later  do  not 
require sending AMPVER command on power-up