Emerson E2 Manuel D’Utilisation

Page de 283
Figure 9-9
 - Relay Output Test Mode for MF I/O Board
9-12
 • 
E2 RX/BX/CX I&O Manual 
9.2.5
 Wiring Outputs to Points
Old 8ROs
The old design of 8RO (P/N 810-3002) used points 
with two terminals on them. To connect output devices to 
these points, wire the point terminals in series with the 
load, so that the path is closed when the 8RO relay is 
CLOSED and open when the 8RO relay is OPEN.
New 8ROs and 8RO-FCs
All other E2-compatible output boards, including the 
new design of 8RO (P/N 810-3005), the 8RO-FC, and 
have Form C contacts. Figure 9-8 shows how to wire the 
three-terminal Form C contact.
One wire of the two-wire 8RO-FC connection should 
always be connected to the middle terminal. The second 
wire must either be connected to the N.C. terminal (if you 
want the path to be closed when the relay is de-energized) 
or the N.O. terminal (if you want the path to be open 
during power failure.
9.2.6
The Output LED
Each output point on an output board has an indicator 
LED that shows the status of the output. This LED is lit to 
show the output is ON, and unlit to show the output is 
OFF.
The definition of ON and OFF in this case is deter-
mined by the position of the fail-safe dip switch (see Table 
9-3
). Therefore, if the output’s switch is UP, an illuminated 
LED means the path is CLOSED, but if the switch is 
DOWN, an illuminated LED means the path is OPEN.
9.2.7
Output Setup in E2
In order for the E2 to properly control devices that are 
hooked to an I/O board, you must first tell the E2 what 
type of output the devices require. This is achieved from 
the Output Definitions/Status screen.
9.2.7.1
Configuring a Point from the 
Output Definitions/Status Screen
To configure a point, go to the Output Definitions/Sta-
tus screen by pressing Alt + O or:
1.
Press 
 to open the Main Menu
2.
Press 
 (System Configuration)
3.
Press 
 (Output Definitions)
The Output Status screen opens:
Figure 9-10
 - Output Status Screen
To configure a point, use the up and down arrow keys 
to move the cursor to the point you wish to set up, and 
press 
 (SETUP).
If you press 
 to set up a 4AO output point, the E2 
will automatically transfer you to the Analog Output 
screen Figure 9-6. For all other output board types, press-
ing 
 will bring up a pop-up menu such as the one 
shown in Figure 9-11. This menu will prompt you to spec-
ify the output as either Digital, Pulse, or One Shot. Press 
 if the output is Digital, press 
 if the output is Pulse, 
press 
 if the output is One Shot, or press 
 to cancel 
setup.