Figure 9-11
 - Output Data Type Pop-Up Menu
The 8RO, 8IO, and MultiFlex Outputs
Input and Output Setup
 • 
9
-
13
Depending upon what type of output you selected, the 
Digital Output, (see Section 9.2.7.3, Setting Up Digital 
Outputs
) Pu
lse Digital Output, or One Shot Digital Output 
screen will appear.
9.2.7.2
Using the Output Definitions/
Status Screen
The Output Definitions/Status screen serves a dual 
purpose. It is both an at-a-glance summary of all points on 
each output board and a menu where output points may be 
selected and configured.
In order for the E2 to properly control devices that are 
hooked to an I/O board, you must first tell the E2 what 
type of output the devices require. This is achieved by 
using the Output Definitions/Status screen.
 (SETUP),  (DEL/MOD),  (LOOK 
UP), and 
 (CANCEL) are the function keys along the 
bottom of the screen available for the Output Definitions/
Status screen.
The Output Definitions/Status screen serves a dual 
purpose. It is both an at-a-glance summary of all points on 
each output board and a menu where output points may be 
selected and configured.
Each record in this screen contains the following infor-
mation about a point:
1. Type (read-only)
Board Type shows which kind of output board the 
point is on. The Board Type field will read either 8RO
8DO, or 4AO for I/O Network 16AI boards, E16AI, and 
8ROE for Echelon Network 16AIe boards.
The last character of the Board Type field also shows 
what type of input the point is defined as. If a point has 
already been defined as an analog or digital input, this 
field will signify its input type with an “A” (for analog) or 
“D” (for digital).
2. Board (read-only)
The point’s board number appears under the Board 
field.
3. Point (read-only)
The point number of each point appears in its record in 
the Point field.
4. Type (read-only)
The Type field shows the output’s data type. Possible 
Types are: A (Analog), D (Digital), O (One Shot), or P 
(Pulse). If the point has not been identified, a “-” will 
appear at the end of the field instead.
5. Application
Select which application you wish to set up inputs to. 
Pressing 
 (LOOK UP) when on a defined point will 
open the Application Selection menu--a list of application 
types currently existing in the box. 
 (CANCEL) will 
cancel this menu.
6. Association
If a point has already been defined and is currently 
being used by an application, the name of the input to 
which the point is connected will be displayed in the Asso-
ciation
 field. 
Association is the application’s user-defined property 
that is associated with the point. Multiple applications 
attached to single input will all be displayed in the Associ-
ation
 field. Pressing 
 (LOOK UP) when on a set 
application will bring up a list of property selections. 
 
(CANCEL) will cancel this menu.
7. Value (read-only)
Value shows the sensor value in the units you select for 
the output type.
9.2.7.3
Setting Up Digital Outputs
Open the Digital Output screen by selecting a Digital 
(D) input from the Output Status screen Figure 9-10 and 
pressing 
 (SETUP).
Digital Outputs are ON when the E2 calls for them to 
be ON, and OFF whenever the E2 calls for them to be 
OFF. Most outputs that directly activate and deactivate 
output devices will need to be set up as the Digital output 
type.