work Status screen (See Figure 10-24). The Network 
Summary screen displays information such as the Subnet 
and Node addresses for each board, and the status of Eche-
lon and I/O boards.
To get to the Network Summary Screen:
1.
Press 
 to open the Main Menu
2.
Press 
 (System Configuration)
3.
Press 
 (Network Setup)
4.
Press 
 (Network Summary)
From the Network Summary screen you can see the 
total (E2) devices online or offline, status, setup screens, 
change board or controller names, configure and commis-
sion devices, delete a device, and view detailed status 
screens of controllers.
After determining if a board is offline, turn to Appen-
10.14 Set Up Echelon 
Network
10.14.1 Specifying Number of 
Devices
To specify the number of devices on the Echelon Net-
work, navigate to the Connected I/O screen:
1.
Press 
 to open the Main Menu
2.
Press 
 
(System Configuration)
3.
Press 
 
(Network Setup)
4.
Press 
 (Connected I/O Boards & Controllers)
Figure 10-25
 - Connected I/O Screen (RX version shown)
After logging in for the first time, the Connected I/O 
screen will ask you to specify how many of each type of 
device will be connected to the E2 you are currently pro-
gramming. (Options will vary depending on the type of 
controller used.)
Unit Number (Echelon Subnet)   Each E2 on the 
Echelon Network must have a different unit number. 
This can be any number from 1 to 255, but each E2’s 
number must be unique. No two E2s on the network 
may have the same unit number.
Enter this number in the Unit Number field. It is rec-
ommended you number the first E2 “1” and number 
the other E2s on the network sequentially (2, 3, 4, 
etc.).
Unit Name   Type a name for the E2 in the Unit 
Name field.
Unit Controllers (Echelon)
Liquid Ctrls (CC100P/CC100LS)   Enter the com-
bined number of pulse valve case controllers 
(CC100Ps) and liquid-side stepper valve case con-
trollers (CC100LSs) in this field.
Suction Controllers (CC100H)   Enter the num-
ber of suction stepper case controllers (CC100Hs) in 
this field.
Circuit Suction (CS100)   Enter the number of suc-
tion lineup circuit controllers (CS100s) in this field.
ESR8 Line Up Boards   Enter the number of ESR 
suction lineup circuit boards (SR100s) in this field.
TD3 Temperature Displays   Enter the number of 
TD3 temperature display units in this field.
EC2- 29x Case Controllers   Enter the number of 
EC2-29x refrigerated case controllers in this field.
EC2-39x Case Controllers   Enter the number of 
EC2-39x refrigerated case controllers in this field.
Echelon 16AI   Enter the number of 16AIe analog 
input boards in this field.
Echelon 8RO   Enter the number of 8ROe analog 
input boards in this field.
10.14.2 Commissioning a Device
Once all records have been created and defined for all 
devices on the Echelon Network, they must be “commis-
sioned.” Commissioning is necessary for the E2 to identify 
and establish communications with all devices on the net-
work.
To start commissioning, open the Network Summary 
screen:
1.
Press 
 to open the Main Menu