Emerson E2 Manuel D’Utilisation

Page de 283
10-22
 • 
E2 RX/BX/CX I&O Manual 
• Users can view alarm notifications and alarm logs 
for all controllers from the Alarm Annunciator.
• Only the Alarm Annunciator needs to be pro-
grammed with alarm filter settings for dial-out, out-
put, and display. All other controllers may be 
programmed to simply send all alarms to the Alarm 
Master via the LonWorks Network. 
10.16.2 Setting up an E2 to be an 
Alarm Annunciator
Any E2 on the network that has a modem or Ethernet 
connection can be set up as an alarm annunciator, but only 
one alarm annunciator per network is allowed. To set up 
from the Main Menu:
1.
Press 
 (System Configuration)
2.
Press 
 
(System Information)
3.
Press 
 (General Controller Info)
4.
Set Alarm Annunc field to Yes.
NOTE: When the E2 is set up as an Alarm An-
nunciator, the Home screen becomes the 
Alarm Log.
If the target E2 is configured as the Annunciator, the 
AnnuncIsHomesScrn property becomes available in 
General Services to select if the Annunciator log is to be 
the Home screen.  The property will default to Yes. If the 
property is set to No, the Home screen will be either the 
default Home screen or the user-selected Home screen.
Figure 10-39
 - Alarm Annunciator
10.16.3 Alarm Dial-Out
Figure 10-40
 - Alarm Setup Menu
One of the E2’s most important alarm reporting fea-
tures is its ability to dial-out to remote sites whenever a 
serious alarm condition occurs. Each E2 is capable of dial-
ing out to up to three sites. The E2 may dial out to a com-
puter, a fax machine, a digital pager, or a printer. To set up 
from the Main Menu:
Dial-out devices are set up in the Dial-out Setup 
screen. To reach this screen:
1.
Press 
(Main Menu)
2.
Press 
 (System Configuration)
3.
Press 
 (Alarm Setup)
4.
Press 
 (Dial-out Setup)