Emerson E2 Manuel D’Utilisation

Page de 283
Figure 11-1
 - Diagram of a Suction Group
SUCTION
PRESSURE
CO
N
D
E
N
S
E
R
DISCHARGE
PRESSURE
LIQUID RECEIVER
CASE CIRC
UIT
OIL 
PRESSURE
CIRCUIT
CASE TEMP
(FOR FLOATING)
LIQUID LINE
SOLENOID
26507005
D
D
D
OIL RESET SWITCHES
Table 11-1 - Suction Group Inputs
Input
Sensor Type
Wiring 
Instructions
Suction Pres-
sure
100 lb. Eclipse 
transducer
Discharge Pres-
sure
500 lb. Eclipse 
transducer
Oil Pressure
200 lb. Eclipse 
transducer
Case Circuit 
Temperature
Temperature
Oil Reset 
Switches
Digital
Table 11-2 - Suction Group Outputs
Output Device
Wire Output Board 
Contacts to:
Set Failsafe Dip 
Switch to:
Notes
Compressor
N.C. 
N.C. (up)
If you want a compressor to be OFF during network/
power loss, use N.O. failsafes instead.
Unloader
N.C.
N.O. (down)
These fail-safe settings are specifically for unloaders.
Liquid Line Sole-
noid (LLS)
N.C.
N.C. (up)
Keeps solenoid energized during network/power loss.
Electric Defrost
N.O.
N.O. (down)
Keeps contacts de-energized during network/power loss.
Condenser Control
Software Overview
 • 
11
-
3
11.2 Condenser Control
An E2 RX is capable of controlling air-cooled or evap-
orative condensers. The E2 RX-300 may control a single 
condenser, while the RX-400 may control up to two con-
densers.
11.2.1 Air Cooled Condensers
An air-cooled condenser consists of one or more fans 
that blow air across a manifold of tubing to cool heated 
refrigerant and condense it into a liquid. The E2 controls 
condensers by activating or deactivating fans in order to 
maintain discharge pressure or temperature at or below a 
chosen setpoint.
A Condenser Control application may use either of two 
strategies to operate air cooled condensers: an air-cooled 
strategy, or a temperature differential (T-D) strategy.
11.2.1.1 Air Cooled Strategy
The air cooled strategy uses a simple PID control loop 
that compares a single Control In input to a PID setpoint. 
The resulting percentage is used to activate the condenser 
fan(s) necessary to bring the input value down below the 
setpoint.
Control inputs for air cooled strategies most commonly 
come from a pressure transducer mounted on either the 
discharge line, the condenser inlet, or the condenser outlet. 
However, temperature sensor values will also be accepted.
11.2.1.2 Temperature Differential 
Strategy
The temperature differential strategy attempts to keep 
a minimum amount of difference between the temperature 
of the refrigerant and the ambient outside temperature.
This strategy begins by determining the temperature of 
the refrigerant coming into the condenser. This can be sup-
plied by either a temperature sensor or pressure transducer 
located near the condenser inlet; if it’s a pressure trans-
ducer, its value will automatically be converted to a tem-
perature value based upon the type of refrigerant.