Emerson E2 Manuel D’Utilisation
Figure 11-3
- Evaporative Condenser Diagram
EVAPORATIVE
CONDENSER
PUMP 2
PUMP 1
WATER
SPRAY
SPRAY
FAN
INLET
OUTLET
DAM
PERS
DISCHARGE
PRESSURE
PRESSURE
COIL
WATER SUMP
TEMPERATURE
TEMPERATURE
26509038
AMBIENT
TEMP
TEMP
WATER SUMP
Table 11-3 - Suction Group Inputs
Input
Sensor Type
Wiring
Instructions
Discharge Pressure
500 lb. Eclipse
transducer
transducer
Ambient Temp
Temperature
Water Sump Temp
(Evap. only)
(Evap. only)
Temperature
(Immersion)
(Immersion)
Override Temp Sen-
sors (Evap. only)
sors (Evap. only)
Temperature
(Pipe-Mount)
(Pipe-Mount)
Table 11-4 - Suction Group Outputs
Output Device
Wire Output Board
Contacts to:
Set Fail-safe Dip
Switch to:
Notes
Condenser Fan
(Single-Speed)
(Single-Speed)
N.C.
N.C. (up)
To ensure condensing during network and power failure,
condenser fans should all be configured normally closed
(N.C.)
condenser fans should all be configured normally closed
(N.C.)
Condenser Fan
Relay (Variable-
Speed)
Relay (Variable-
Speed)
N.C.
N.C. (up)
The fan should operate at 100% during loss of communi-
cation with E2.
cation with E2.
Dampers (Evap.
only)
only)
N.C.
N.C. (up)
Dampers should be open during communication loss
(N.C.).
(N.C.).
Evaporator
Pumps (Evap.
only)
Pumps (Evap.
only)
N.C. (see note)
N.C. (see note)
Some condensers have dual pumps that cycle at even
intervals. One pump should be wired N.C. and the other
N.O., so that only one pump runs during communication
loss.
intervals. One pump should be wired N.C. and the other
N.O., so that only one pump runs during communication
loss.
Variable-Speed
Fan Output (to
inverter)
Fan Output (to
inverter)
None (analog
point)
point)
None (analog
point)
point)
This 4AO or 8IO analog point sends the 0-100% fan
speed signal to the inverter.
speed signal to the inverter.
Standard Circuits
Software Overview
•
11
-
5
11.3 Standard Circuits
Refrigerated cases that do not use case controllers are
controlled by Standard Circuit applications. In a Standard
Circuit application, the E2 is responsible for all case mon-
itoring and control; it uses the RS485 I/O Network to both
gather case temperature inputs and activate or deactivate
the liquid line solenoids, defrost modes, and fans. Also,
circuits that use ESR8s and MultiFlex ESRs are controlled
using Standard Circuits.
Circuit application, the E2 is responsible for all case mon-
itoring and control; it uses the RS485 I/O Network to both
gather case temperature inputs and activate or deactivate
the liquid line solenoids, defrost modes, and fans. Also,
circuits that use ESR8s and MultiFlex ESRs are controlled
using Standard Circuits.
NOTE: Do not set up a Standard Circuit appli-
cation for a case that uses a CC-100 or CCB
case controller. These cases must use Case Cir-
cation for a case that uses a CC-100 or CCB
case controller. These cases must use Case Cir-
cuit Control applications (see Section 11.4, Case Con-
trol Circuits).
trol Circuits).