Electric Defrost
Electric defrost uses electric heaters to defrost the 
evaporator coil. During electric defrost, the application 
will turn the Defrost output ON to activate the heaters con-
nected to the output.
Any user-defined Pump Down and Run-Off times will 
be observed as normal.
11.3.2.3 Defrost Termination
Both the start and the end times of a defrost cycle are 
determined by the user. The Pump Down, Defrost, and 
Run-Off stages all have fixed durations, and when the last 
stage of the cycle is complete, defrost is terminated.
However, a Standard Circuit application may be pro-
grammed to terminate the Defrost stage of the defrost 
cycle early if the temperature inside the case rises above a 
fail-safe temperature setpoint (called the termination set-
point). For certain defrost types, defrost heat may also be 
“pulsed” in order to keep the temperature below the set-
point without terminating defrost.
Pulsed Defrost
Figure 11-4
 - Defrost Termination (Pulsed)
Pulsed Defrost is only available if the circuit is using 
heated defrost, such as Electric or Hot Gas defrost.
Pulsed Defrost is similar to the Temperature Termina-
tion strategy outlined iSection 11.3.2.3, except a defrost 
cycle always continues for the full programmed duration.
When the termination temperature rises above the set-
point, defrost does not end. Instead, the defrost heat is 
turned OFF until the case temperature falls below the set-
point, at which time the output will come back ON to con-
tinue heating.
Figure 11-4 illustrates what happens in a pulsed 
defrost cycle. In this example, the case reaches its termina-
tion temperature approximately 2/3 of the way into its 
defrost cycle. Defrost continues, but defrost heat is turned 
OFF until the temperature falls below the setpoint, at 
which point the heat is turned back ON. 
Defrost heat will continue to be pulsed in this manner 
until the defrost time has passed. The defrost cycle will 
then begin the Run-Off period, and then restart refrigera-
tion.
11.3.2.4 Emergency Defrost
When necessary, a user can initiate an emergency 
defrost cycle in a circuit. Emergency defrost cycles are 
similar to normal defrost cycles, except an emergency 
defrost cycle will ignore all calls for termination and 
remain in defrost for the entire programmed defrost time. 
For cases using a pulsed defrost strategy, this means the 
defrost heat will not be pulsed during emergency defrost.
 Emergency defrosts are initiated by the user from the 
11.3.2.5 Hot Gas Defrost with ESR8 and 
MultiFlex ESR
If an ESR8 or MultiFlex ESR is used on a circuit that 
uses hot gas defrost, values for circuits in defrost are 
forced OPEN (100%) to allow hot gas to flow through the 
evaporators. 
11.3.3 Clean and Door Switches
11.3.3.1 Clean Switches
A Standard Circuit application may be configured to 
entirely shut down a case circuit so that it may be cleaned 
or serviced. A case circuit enters clean mode when it 
receives a signal from an input called the clean switch.
Clean switches may be set up as either “Switched” or 
“Timed.” If a clean switch is configured as “switched,” the 
circuit enters clean mode when the switch is turned ON, 
and it remains in clean mode until the switch is turned 
OFF. If a clean switch is configured as “timed,” the circuit 
enters clean mode when the switch is turned ON, and it 
remains in clean mode for a fixed user-defined amount of 
time.
During clean mode, the Fan, Defrost, and Refrigera-
tion Solenoid outputs are all turned OFF, and the liquid 
line solenoid is CLOSED.
If desired, a notice may be sent to the E2’s Alarm Log 
so that the E2 can keep track of clean modes and times.