Emerson E2 Manuel D’Utilisation
2-4
•
E2 RX/BX/CX I&O Manual
custom cell in Einstein/E2
Table 2-5 - Gateway Board Models
P/N
Gateway Model
810-3500
RF Gateway
810-3700
IRLDS II Gateway
810-3760
RLDS Gateway
810-3710
Danfoss MicroCool Gateway
810-3711
Woodley Case Controller Gateway
810-3712
Woodley Pack Controller Gateway
810-3720
Cutler Hammer Breaker Gateway
810-3721
Square D Breaker Gateway
2.2.2
MultiFlex Boards
The MultiFlex line of control system boards provides a
wide variety of input, output, and smart control solutions,
all of which are based on a single universal hardware plat-
form. The board design uses flash-uploadable firmware
and plug-in expansion boards to configure the base plat-
form board and apply it for use as an input board, relay
output board, analog output board, or a combination I/O
board.
all of which are based on a single universal hardware plat-
form. The board design uses flash-uploadable firmware
and plug-in expansion boards to configure the base plat-
form board and apply it for use as an input board, relay
output board, analog output board, or a combination I/O
board.
2.2.2.1
MultiFlex 16 Input Board
Figure 2-6
- MultiFlex 16 Input Board
The MultiFlex 16 input board offers sixteen combina-
tion analog/digital input points for use by Emerson Retail
Solutions E2, Einstein, and REFLECS control systems.
The MultiFlex 16 may be used in retrofits with no addi-
tional hardware or software setup or upgrades.
Solutions E2, Einstein, and REFLECS control systems.
The MultiFlex 16 may be used in retrofits with no addi-
tional hardware or software setup or upgrades.
The MultiFlex 16 is designed to be 100% compatible
with the previous generation of Emerson Retail Solutions
input boards (the 16AI),
input boards (the 16AI),
communicates with the site con-
troller via an RS485 connection to a REFLECS COM
A&D Network or an E2 I/O Network. Dip switches on the
board set the network ID (board number) and baud rate.
A&D Network or an E2 I/O Network. Dip switches on the
board set the network ID (board number) and baud rate.
The board also provides both +5VDC and +12VDC
output voltage points for use in powering transducers or
other input devices that require power.
other input devices that require power.
The MultiFlex 16 has a Hand-held Terminal interface
Section 2.2.4, Hand-held Terminal (P/N 814-3110) that
may be used by technicians to view the input voltage and
engineering unit values for each input point without need
of a voltmeter or front panel controller display.
may be used by technicians to view the input voltage and
engineering unit values for each input point without need
of a voltmeter or front panel controller display.
Table 2-6 shows the part number of the MultiFlex 16.
Table 2-6
- MultiFlex 16 Input Board Model
P/N
Model Name
Description
810-3013
MultiFlex 16
16 analog/digital in-
puts, no outputs
puts, no outputs
The MultiFlex 16 is designed with several features
that make it easy to install, wire, and configure. These
main user interface features are shown in Figure 2-6.
main user interface features are shown in Figure 2-6.
2.2.2.2
MultiFlex Combination Input/
Output Boards
Figure 2-7
- MultiFlex Combination Input/Output Board (Side
View)