Emerson E2 Manuel D’Utilisation

Page de 283
2-6
 • 
E2 RX/BX/CX I&O Manual 
2.2.2.3
MultiFlex CUB
The MultiFlex Condensing Unit Board (CUB) is a 
“smart” input/output board designed to control single con-
densing units. A single condensing unit is a self-contained 
compressor and condenser bearing unit which controls 
refrigeration in a single case line-up or walk-in cooler.
 The MultiFlex CUB uses the same general hardware 
configuration as a MultiFlex 168AO. It is equipped with a 
processor and extra memory to allow it to control com-
pressors, condensers, refrigeration, and defrost for a single 
condensing unit using on-board I/O and control algo-
rithms.
The MultiFlex CUB has its own installation and opera-
tion manual, (P/N 026-1705).
2.2.2.4
MultiFlex RTU (BX and CX Only)
Similar in design to the MultiFlex combination input/
output boards, the MultiFlex RTU board is designed spe-
cifically for operating package rooftop HVAC units as part 
of an E2 BX or REFLECS BCU building control system. 
The MultiFlex RTU is designed to be a replacement for the 
previous generation ARTC, and is 100% compatible with 
all legacy E2 BX and BCU systems.
The MultiFlex RTU board has 16 analog inputs, 8 
relay outputs and 4 analog outputs. Most of these I/O 
points are reserved for sensors and input devices required 
to read environmental data (such as space and supply air 
temperature) and control all output devices that control the 
environment (such as heat/cool stages and dampers). Both 
auxiliary inputs can be configured for a variety of sensor 
types including any type of linear sensor. For linear sen-
sors, the auxiliary inputs can be configured as Satellites. 
By doing this, the minimum and maximum voltage and 
minimum and maximum Engineering Unit parameters are 
user configurable for these inputs. The RTU relay outputs 
are rated for line voltage (240VAC).
The RTU board controls the rooftop unit directly with 
its built-in heating, cooling, and humidity control algo-
rithms. It may operate in stand-alone mode, or it may 
interface with an E2 BX or BCU to control the store envi-
ronment in zones and pass along logging and alarm infor-
mation.
The MultiFlex RTU has its own installation and opera-
tion manual, (P/N 026-1706).
2.2.2.5
MultiFlex Rooftop Control Board 
(RCB) (BX and CX Only)
The MultiFlex Rooftop Control Board (RCB) 
(P/N 810-3062) is a rooftop HVAC control board for use 
either as a stand-alone controller or in zone control appli-
cations using a Emerson Retail Solutions E2 BX building 
control system. The MultiFlex RCB is capable of con-
trolling heat and cool stages, fans, humidification and 
dehumidification devices, economizers using on-board I/O 
and control algorithms, as well as monitor and interact 
with other building control systems and peripherals (such 
as smoke alarms and CO
2
 sensors).
The RCB is an improved version of the MultiFlex 
RTU. The RCB has sixteen fully configurable analog and 
digital input points, whereas the RTU has only eight 
inputs, two of which are configurable. The RCB has four 
analog outputs for use in controlling variable speed fans, 
economizers or modulating heating and/or cooling valves, 
whereas the RTU has only two analog outputs for use only 
with VS fans and economizers. The RCB also features a 
more sophisticated HHT interface and updated algorithms 
for controlling heating, cooling, dehumidification, and air 
quality.
The MultiFlex RCB-P (pulse control board P/N 810-
3076) uses an alternate control strategy that incorporates 
logic for controlling heating and cooling functions.
The MultiFlex RCB has its own installation and opera-
tion manual, (P/N 026-1707).
Figure 2-9
 - MultiFlex RCB
1    Input Power (24VAC)
2    RS485 I/O Network
3    RCB Inputs 1-8
4    RCB Inputs 9-16
5    Network ID Dip Switches (S3, S4)
7    Board Status LEDs
      (Code A, Code B, General Status)
12   Relay Output Fuses
       (2A Rated, 250V Slow-blow
13   Relay Status LEDs
14   Output Fail-Safe Switches
15   Analog Outputs
8    DC Power Outputs
      (3 at +5VDC, 1 at +12VDC)
9    RS485 Termination Jumpers
11   Relay Output Connector
10   Hand-Held Terminal Jack
16   Network Status LEDs
2.2.2.6
MultiFlex PAK Board
The PAK is a distributed pack (rack) controller that 
controls compressors and condenser fans. The PAK can 
control up to 8 compressor groups containing up to 16 
compressors. The compressor control strategy is Fixed 
Steps with setpoint/deadband using ON and OFF delays. 
Up to 20 Fixed Steps can be configured.