Form 6104 BCF23-R05
Annual Service
Replace the oil supply line fi lter.  The  line  fi lter 
cartridge must be replaced to avoid contamination of 
the fuel unit and nozzle.
Inspect the oil supply system. All fi ttings should be 
leak-tight. The supply lines should be free of water, 
sludge and other restrictions.
Remove and clean the pump strainer if applicable.
Replace the nozzle with the exact brand, pattern, gph, 
fl ow rate and spray angle.
Clean and inspect the electrodes for damage, replacing 
any that are cracked or chipped.
Check electrode tip settings. Replace electrodes if tips 
are rounded.
Inspect the igniter spring contacts.
Clean the cad cell lens surface, if necessary.
Inspect all gaskets. Replace any that are damaged or 
would fail to seal adequately.
Inspect the combustion head and air tube. Remove 
any carbon or foreign matter. Replace all damaged 
units with exact parts.
Clean the blower wheel, air inlet, air guide, burner 
housing and static plate of any lint or foreign 
material.
If motor is not permanently lubricated, oil motor with 
a few drops of SAE 20 nondetergent oil at each oil 
hole. DO NOT over oil motor. Excessive oiling can 
cause motor failure.
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
Perform Regular Maintenance
Do not tamper with the burner or controls or make 
any adjustments unless you are a trained and qualifi ed 
service technician.
To ensure continued reliable operation, a qualifi ed 
service technician must service this burner annually.
More frequent service intervals may be required in 
dusty or adverse environments.
Operation and adjustment of the burner requires 
technical training and skillful use of combustion test 
instruments and other test equipment.
y
y
y
y
Tampering with or making incorrect 
adjustments could lead to equip-
ment malfunction and result in 
asphyxiation, explosion or fi re.
Annual Professional 
Service Required
Check motor current. The amp draw should not 
exceed the nameplate rating.
Check all wiring for secure connections or insulation 
breaks.
Check the pump pressure and cutoff function.
Check primary control safety lockout timing.
Check ignition system for proper operation.
Inspect the vent system and chimney for soot 
accumulation or other restriction.
Clean the appliance thoroughly according to the 
manufacturer’s recommendations.
Check the burner performance. Refer to the section 
“Set combustion with test instruments”.
It is good practice to make a record of the service 
performed and the combustion test results.
Monthly maintenance — by owner
Observe combustion air openings and vent system 
for integrity. Openings must be clean and free of 
obstructions.
Check oil lines and fi ttings to verify there are no 
leaks.
Observe burner ignition and performance to verify 
smooth operation.
Shut the system down if you observe abnormal or 
questionable operation. Call a qualifi ed service agency 
for professional inspection and service.
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ