Figure 1.  Min. Combustion Chamber Dimensions
Verify fi ring rate
Refer to appliance manufacturer’s instructions (if 
available) for fi ring rate and nozzle selection. Otherwise, 
the maximum recommended fi ring rate for the burner 
depends on the length of the fi ring chamber and the 
distance from the burner center to the chamber fl oor. 
Verify that the chamber dimensions are at least as large 
as the minimum values given in Figure 1. If the appliance 
dimensions are smaller than recommended, reduce the 
fi ring rate accordingly.
‰
y
Table 1 - Nozzle Capacities
Rated gph @  
100 psig
Pressure - pounds per square inch
125
140
150
1.35
1.51
1.60
1.65
1.50
1.68
1.77
1.84
1.65
1.84
1.95
2.02
1.75
1.96
2.07
2.14
2.00
2.24
2.37
2.45
2.25
2.52
2.66
2.76
2.50
2.80
2.96
3.06
2.75
3.07
3.25
3.37
3.00
3.35
3.55
3.67
Firing Rate
Minimum Dimensions
(refractory-lined)
(wet-base boilers)
A
L
A
L
1.65 to 2.00 gph
5.5”
12.0”
5.5”
12.0”
2.00 to 3.75 gph
6.0”
15.0”
6.0”
20.0”
Air Tube 
Length            
(Dimension T)
A.T.C. Codes
(A.T.C. = Air Tube Combination)
Tube A
Tube B
0
5.75”
CF56KY
CF56KZ
10.00”
CF100KY
CF100KZ
14.00”
CF140KY
CF140KZ
X
 Install burner with 2o pitch as shown.
X
Figure 2 - Air Tube Mounting Dimensions
Verify air tube
The information in this section may be disregarded if the 
air tube is supplied by the appliance manufacturer.
Two tube arrangements are available –
 Tube 
A — 1.65 to 2.00 GPH 
 Tube 
B — 2.00 to 3.75 GPH 
Maximum fi ring capacity depends on the fi rebox pressure. 
Use Table 2 to verify the correct air tube type for the fi r-
ing rate required. Use Tube B only when Tube A cannot 
provide the fi ring rate required.
See Figure 2 to verify the correct air tube length and air 
tube combination code.
‰
y
y
y