Set dimension Z
Loosen fastener c in Figure 6. Slide the nozzle line and 
plate assembly until dimension Z in Figure 5 is 1-1/2”   
±1/16”
. When dimension Z (from end of air tube to fl at 
area of front face of head) is correctly set, tighten acorn 
nut c
Attach the oil line from the oil valve to the nozzle line end. 
Tighten securely.
Before proceeding, check dimension Z once again. Loosen 
acorn nut c if necessary to reposition the nozzle line. Once 
dimension Z is set, do not loosen the acorn nut c again
Note that for the setting of fastener d, refer to Initial Head 
Position
 procedure on Page 10.
‰
y
y
y
Figure 6 - Adjusting plate assy.
Legend (Figures 5 and 6)
c
Bottom acorn nut
d
Fastener
The burner is shipped without the by-pass plug in-
stalled.
Intall the by-pass plug in two-pipe oil supply systems 
ONLY.
y
y
Failure to comply could cause immediate pump 
seal failure, pressurized oil leakage and the po-
tential for a fi re and injury hazard.
Do Not Install By-pass 
Plug with 1-Pipe System 
e
Indicator adjusting plate
f
Secondary adjusting plate
Install the oil tank and oil lines in accordance with all 
applicable state and local codes.
Size the oil supply and return lines using the guidelines 
given in the fuel unit literature included in the literature 
envelope. Oil line fl ow rate will equal the burner rate for 
one-pipe systems. For two-pipe systems, refer to Table 2 
for the fuel unit gear set capacity - the rate at which fuel 
is recirculated when connected to a two-pipe system. Size 
two-pipe oil lines based on this fl ow rate.
Use continuous lengths of heavy-wall copper tubing, 
routed under the fl oor where possible. Do not attach fuel 
lines to the appliance or to fl oor joists if possible. This will 
reduce vibration and noise transmission problems.
Install an oil fi lter sized to handle the fuel unit gearset fl ow 
capacity (Table 2) for two-pipe systems. Size the fi lter 
for the fi ring rate for one-pipe systems. Locate the fi lter 
immediately adjacent to the burner fuel unit.
y
y
y
y
Carefully install the oil supply lines, fi ttings and com-
ponents using the guidelines provided in this section.
The oil supply must comply with the latest edition 
of NFPA 31 (Canada CSA B139) and all applicable 
codes.
 Do NOT install valves in return lines.
If the oil supply inlet pressure to the pump exceeds 3 
psig or for gravity feed systems, install an oil safety or 
pressure reducing valve (Webster OSV, Suntec PRV or 
equivalent). 
y
y
y
y
Failure to properly install the oil 
supply system could cause oil 
leakage, equipment malfunction, 
puff-back of hot gases, heavy 
smoke, asphyxiation, explosion and 
fi re hazards.
Install Oil Supply To 
Specifi cations
Fuel unit by-pass plug
‰
Figure 5 - Nozzle line assembly in burner
1-1/2”
Insert burner
Position the burner in the front of the appliance and loosely 
tighten the nuts on the mounting studs. The burner should 
be pitched downward 2° as shown in Figure 3.
Secure the burner to the appliance by tightening the nuts 
on the burner fl ange mounting studs.
‰
y
y
The CF375 burner is shipped without the by-pass plug 
installed in the fuel line.
The by-pass plug must NOT be installed when using 
with a one-pipe oil system.
The by-pass plug MUST be installed when using a 
two-pipe oil system
.
Oil supply/return lines
y
y
y
‰