Never use Tefl on tape on fuel oil fi ttings. 
Tape fragments can lodge in fuel line components 
and fuel unit, damaging the equipment and pre-
venting proper operation.
Use oil-resistant pipe sealant compounds.

Damage to the pump could cause impaired burn-
er operation, oil leakage and appliance soot-up.
Do Not Use Tefl on Tape
!
!
CAUTION
Fuel Line Installation 
Inspect/Prepare Installation Site
Figure 3. – Mounting Burner in Appliance
 
Prepare the Burner
 General
   In most cases, the burner is ready to mount to the 
appliance.  There can be situations where the burn-
er needs to be reconfi gured to perform properly in 
the appliance.  Review the appliance manufactur-
er’s  specifi cations prior to installing to determine if 
any modifi cation is required to properly confi gure 
the burner. 
  Instruction on how to perform the following burner 
preparation  tasks can be found in the Professional 
Maintenance section.
Remove / install burner nozzle
Check head/air adjusting plate
Mount Burner on Appliance
  Verify that the air tube installed on the burner   pro-
vides the correct insertion depth. Refer to Figure 
3.
  The end of the air tube should normally be 
1/4
” back 
from the inside wall of the combustion chamber. 
Never allow the leading edge of the retention ring 
to extend into the chamber, unless otherwise speci-
fi ed by the appliance manufacturer.  
  Bolt the burner to the appliance using the factory-
welded fl ange.  

 To further protect the fuel supply system and reduce noz-
zle orifi ce plugging with fi ring rates below 0.75 gph, a dual 
fi ltration system can be installed. This typically consists of 
a 50 micron primary fi lter, located near the fuel tank and a 
secondary fi lter rated for at least 10 microns located near 
the burner. 
NOTICE
For protection in the event of fi re, some states require the 
shutoff valves to be a fusible-handle design. R.W. Beck-
ett Corporation recommends this design as good industry 
practice for all installations.
NOTICE
  For fuel line installation, continuous lengths of heavy 
wall copper tubing are recommended. Always use 
fl are fi ttings. Never use compression fi ttings.
 Always 
install 
fi ttings in accessible locations. To 
avoid vibration noise, fuel lines should not run 
against the appliance or ceiling joists.
Fuel Line Valves and Filter 
  Install two high quality oil duty rated shutoff valves 
in accessible locations on the oil supply line. Locate 
one close to the tank and the other close to the 
burner, upstream of the fi lter.
  Also install a generous capacity fi lter, rated for 50 
microns or less, inside the building between the 
fuel tank shutoff valve and the burner. Locate both 
the fi lter and the valve close to the burner for ease 
of servicing. 
3 GPH 150-200 PSI 3450 R
PM
4 GPH
GPH 100-150
100-150 PSI
PSI 3450
3450 RPM
RPM
BY-PASS
INLET
A2EA-6520
A2EA-6520
NO. 2 & LIGHTER FUEL
Exclusively for Beckett
NO. 2 FUEL
Made by Suntec
Made by Suntec
INLET
Beckett
USE
USE ONLY
ONLY WITH
WITH
VALVE ON DELAY