Start the Burner and Set Combustion
Figure 4. – Typical Wiring, R7184 Primary Control
SK9359
7.  RECYCLE. If the fl ame is lost while the burner is 
fi ring, the control shuts down the burner, enters a 60 
second recycle delay, and then repeats the above 
ignition sequence. If fl ame is lost three times in a 
row, the control locks out to prevent cycling with 
repetitious fl ame loss due to poor combustion.
8.  BURNER MOTOR-OFF DELAY. The fuel valve 
is closed and the burner motor is kept on for the 
selected motor-off delay time before the control re-
turns the burner to standby.
1.  STANDBY. The burner is idle, waiting for a call for 
heat. When a call for heat is initiated, there is a 3-
10 second delay while the control performs a safe 
start check.
2.  VALVE-ON  DELAY. The ignition and motor are 
turned on for a 15 second valve-on delay.
3.  
TRIAL FOR IGNITION (TFI). The fuel valve is 
opened. A fl ame should be established within the 
15 second lockout time.
4.  LOCKOUT.  If  fl ame is not sensed by the end of 
the TFI, the control shuts down on safety lockout 
and must be manually reset. If the control locks out 
three times in a row, the control enters restricted 
lockout. 
5.  IGNITION  CARRYOVER.  Once  fl ame is estab-
lished, the ignition remains on for 10 seconds to 
ensure fl ame stability before turning off. If the con-
trol is wired for intermittent duty ignition, the ignition 
unit stays on the entire time the motor is running.
6.  RUN. The burner runs until the call for heat is sati-
fi ed. The burner is then sent to burner motor off 
delay, if applicable, or it is shut down and sent to 
standby.
61351
Feature
Interrupted 
ignition
Limited reset, 
Limited recycle
Diagnostic LED, 
cad cell indicator
Valve-on 
delay
Burner motor 
off delay
Alarm Con-
tacts
R7184A
YES
YES
YES
R7184B
YES
YES
YES
YES
R7184P
YES
YES
YES
YES
YES
Optional
Control System Features