Alarm and fault messages 
4.2 Alarm and fault messages 
38 
Table 4-22 Fault 94 
(Alarm) Profibus system has failed 
Condition 
The S7 has detected serious errors on the Profibus 
Equalizing current on the Profibus cable shield 
The Profibus cable shield is not properly connected 
Terminating resistors are not correctly set 
No power supply available at the beginning or end of the 
Profibus line 
External conducted interference 
Causes 
Defect on Profibus node(s) 
Provide equipotential bonding between individual 
inverters 
Connect the cable shields correctly 
Change the Profibus cabling 
 
Possible 
remedial 
measures 
Replace the defective printed circuit boards 
 
Table 4-23 Fault 95 
(Alarm) Grid voltage outside tolerance 
Condition 
The CU has detected that the measured grid frequency 
is outside the set tolerance limits 
Incorrect phase sequence 
Causes 
Fluctuations of the line frequency 
 
Measures 
Connect up the cables correctly (change the phases, 
phase sequence must be clockwise)