Siemens Water Heater SINVERT 350 Manuel D’Utilisation
Alarm and fault messages
4.2 Alarm and fault messages
39
Table 4-24 Fault 96
(Alarm) Grid voltage outside tolerance
Condition
The CU has detected that the grid voltage is outside the
set tolerance limits
Grid voltage outside tolerance
set tolerance limits
Grid voltage outside tolerance
o
No power supply
o
Unstable power supply
o
Medium-voltage breaker has tripped (if
installed)
o
Control
oscillations
o
Supply point overloaded (voltage rise as a
result of additional load)
o
Control (CU software) is not working correctly
Causes
Defective components
o
Transformer
o
AC
capacitors
o
Restrictor
o
AC
fuses
o
Drive
Adjust the parameter settings
Close the medium-voltage breaker
Close the medium-voltage breaker
Measures
Replace the defective components
Table 4-25 Fault 97
(Alarm) No checkback signal from the DC link contactor
Condition
The CU has detected that the grid voltage is outside the
set tolerance limits
No checkback signal on the S7
Interface contactor has not responded
set tolerance limits
No checkback signal on the S7
Interface contactor has not responded
o
Interface contactor is defective
o
Interface contactor has not operated
o
Interface contactor is blocked
o
Insufficient current supply to contactor coils
Fault in signal power supply
Wire break
Wire break
Causes
S7 relay output module defective
Repair the interface contactor
Replace the interface contactor
Repair the power supply
Use a higher-capacity power supply
Replace the cabling
Repair the interface contactor
Replace the interface contactor
Repair the power supply
Use a higher-capacity power supply
Replace the cabling
Measures
Replace the S7 relay output module
Table 4-26 Fault 98