Alarm and fault messages 
4.2 Alarm and fault messages 
39 
Table 4-24 Fault 96 
(Alarm) Grid voltage outside tolerance 
Condition 
The CU has detected that the grid voltage is outside the 
set tolerance limits 
Grid voltage outside tolerance 
o
  No power supply 
o
  Unstable power supply 
o
  Medium-voltage breaker has tripped (if 
installed) 
o
 Control 
oscillations 
o
  Supply point overloaded (voltage rise as a 
result of additional load) 
o
  Control (CU software) is not working correctly
Causes 
Defective components 
o
 Transformer 
o
 AC 
capacitors 
o
 Restrictor 
o
 AC 
fuses 
o
 Drive 
Adjust the parameter settings 
Close the medium-voltage breaker 
 
Measures 
Replace the defective components 
 
Table 4-25 Fault 97 
(Alarm) No checkback signal from the DC link contactor 
Condition 
The CU has detected that the grid voltage is outside the 
set tolerance limits 
No checkback signal on the S7 
Interface contactor has not responded 
o
  Interface contactor is defective 
o
  Interface contactor has not operated 
o
  Interface contactor is blocked  
o
  Insufficient current supply to contactor coils 
Fault in signal power supply 
Wire break 
Causes 
S7 relay output module defective 
Repair the interface contactor 
Replace the interface contactor 
Repair the power supply 
Use a higher-capacity power supply 
Replace the cabling 
 
Measures 
Replace the S7 relay output module 
 
 
 
 
Table 4-26 Fault 98