Page  16
7014-082D
September 1, 2008
CB 1200 Pellet Stove 
6
Mobile Home
1. 
An outside air inlet must be provided for the combustion 
air and must remain clear of leaves, debris, ice and/or 
snow.  It must be unrestricted while the appliance is 
in use to prevent room air starvation which causes 
smoke spillage.  Smoke spillage can also set off smoke 
alarms.  
2.  The combustion air duct system must be made of 
metal.  It must permit zero clearance to combustible 
construction and prevent material from dropping into 
the inlet or into the area beneath the dwelling and 
contain a rodent screen.
3. 
The appliance must be secured to the mobile home 
structure by bolting it to the floor (using lag bolts).  
Use the same holes that secured the appliance to the 
shipping pallet.
4. 
The appliance must be grounded with #8 solid copper 
grounding wire or equivalent, terminated at each end 
with an NEC approved grounding device.
5.  Refer to Clearances to Combustibles and floor pro-
tection requirements on pages 8  & 9 for listings to 
combustibles and appropriate chimney systems.
6.  Use silicone to create an effective vapor barrier at 
the location where the chimney or other component 
penetrates to the the exterior of the structure.
7. 
Follow the chimney manufacturer’s instructions when 
installing the vent system for use in a mobile home.
8. 
Installation shall be in accordance with the Manufactur-
ers Home & Safety Standard (HUD) CFR 3280, Part 
24.
CAUTION
Maintain structural integrity of mobile home:
•   Floor, wall, ceiling and/or roof.
Do NOT cut through:
•  Floor joist, wall, studs or ceiling trusses.
•  Any supporting material that would affect the structural 
integrity.
Never install in a sleeping room.
WARNING
Installation must comply with Manufactured Home and 
Safety Standard (HUD), CFR 3280, Part 24.
WARNING
You must use a Quadra-Fire Outside Air Kit 
for installation in a mobile home.
A. Mobile Home Installation
Figure 16.1
CAUTION
Never draw outside combustion air from:
•  Wall, floor or ceiling cavity
•  Enclosed space such as an attic or garage
Spark Arrestor Cap 
Roof Flashing 
Storm Collar 
Joist Shield/Firestop 
Approved Class “L” o
“PL” Pellet Vent