Troubleshooting
32
FAULT
CAUSE
CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.    
•  Check external line switch, fuse, or breaker.
•  Check position of ON/OFF switch. Turn switch to the 
   ON position.
• Check 120 VAC through the ON/OFF switch.  No 
  voltage through switch, replace switch.
- Bad wiring connection.
•  Check wiring harness connection between the display 
  board and the main control board.  Connect the harness 
  at both points.
- Blown fuse.  
• Replace fuse F6 on the main control board, see 
 
 
 
 
 
   
  FIG. 3-1 on page 31 of this manual.
- Bad display board.  
•  Replace board.
- Bad main control board. 
•  Replace main control board.
No Burner 
Operation
- Main control board temperature set point 
 satisfied.
•  Review temperature setting.
- Remote thermostat satisfied.  
•  Review remote thermostat setting.
Outside air temperature above Warm 
  Weather Shutdown (WWSD) set point for 
  main control board.  
• Check location of outside air sensor.  Check 
  resistance of outdoor air sensor and compare to Table 
  3D on page 33 of this manual.
- Unit locked out on fault.  
• Consult display for specific fault.  Refer to fault 
  descriptions on pages 35 - 42 of this manual for 
 corrective 
actions.
Unit Does Not 
Modulate to 
100%
- Ramp delay active.  
• Check ramp delay parameter settings.  Optional PC 
  software required.  
•  Turn ramp delay feature off.  See page 18 of this 
  manual for instructions on how to turn this feature off.
- Boiler controlled by BMS.  
• Check BMS parameter settings.  Optional PC 
 software 
required.
- Outlet temperature too high.  
- Delta T too high.  
Table 3A Troubleshooting Chart - No Display