Lochinvar Copper-fin II/IIE Boiler, Water Heater and Pool Heater 402 - 2072 Manuel D’Utilisation
3
Troubleshooting
34
FAULT
CAUSE
CORRECTIVE ACTION
Noisy
Operation
- Gas supply problem.
• Refer to the Gas Connections Section of the
Installation and Operation Manual for detailed
information concerning the gas supply.
information concerning the gas supply.
- Gas/air mixture problem.
• Refer to the Checking Manifold Gas Pressure and
Combustion Analysis Procedure on pages 27 and 28 of
this manual for the proper settings. Verify
that the vent/air intake lengths do not exceed the
maximum listed in the Venting section of the
Installation and Operation Manual.
this manual for the proper settings. Verify
that the vent/air intake lengths do not exceed the
maximum listed in the Venting section of the
Installation and Operation Manual.
- Dirty/damaged burner.
• Refer to pages 26 and 27 in this manual for the burner
removal and inspection procedure. Clean or replace the
burner as necessary.
removal and inspection procedure. Clean or replace the
burner as necessary.
- Low water flow through the heat exchanger. • Refer to the Water Connections Section of the
Installation and Operation Manual for
minimum flow rates. Verify that the appliance is piped in
a primary/secondary fashion and that the appliance and
system pump are running on a call for heat.
a primary/secondary fashion and that the appliance and
system pump are running on a call for heat.
- Air in the piping system.
• Properly purge all air from the piping system.
- Low system water pressure.
• Verify system pressure is a minimum of 12 PSI.
No Pump
Operation -
Boiler Pump
System Pump
or
DHW Pump
- Faulty pump relay.
• Replace relay.
- Faulty pump.
• Replace pump.
- Internal fault on control board.
• Check fuse F5.
• Replace main control board.
Note: Make sure the boiler pump horse power (hp) does
not exceed 1 hp.
not exceed 1 hp.
Relief Valve
Opening
-
System pressure exceeds relief valve
setting.
•
Lower the system pressure below the rating of
the supplied relief valve or replace the standard relief
valve with a higher rated valve up to the maximum
pressure of the heat exchanger.
valve with a higher rated valve up to the maximum
pressure of the heat exchanger.
- Improperly sized expansion tank.
• Install properly sized expansion tank.
- Outlet water temperature in excess of 210°.
• Check set point of temperature control.
• Check temperature rise across heat exchanger. Refer to
the temperature rise chart in the Water
Connections Section of the Installation and Operation
Manual.
Manual.
Table 3D Troubleshooting Chart - Noisy System
Copper-fin II/IIE Boiler, Water Heater and Pool
Service Manual