Sequence of operation
Table 1A_Sequence of Operation - Space Heating and DHW
1  
Service 
(continued)
OPERATION
DISPLAY
1.  The manual reset high limit (optional) must be closed before 
any action will take place.
HTR: Standby
OUT: 123.8F(129)
2. Upon a call for heat the control turns on the appropriate 
pumps (system and boiler pumps for space heating; DHW 
pump for DHW call).  The flow switch and low water cutoff 
(if equipped) must close. 
 
HTR: Standby
OUT: 123.8F(129)
3.  •  The gas pressure switch(es) (if equipped) must close.
 
•  The louver proving input must close.
 
•  If the air pressure switch is open, the prepurge cycle then 
   begins by starting the combustion blower.  Once started, 
   the air pressure switch must close. 
HTR: Standby
OUT: 123.8F(129)
4.  After the 15 second prepurge, the blower slows down and 
the hot surface igniter (HSI) is energized.  The HSI is heated 
for at least 20 seconds.  
HTR: PREPURGE
OUT: 123.9F(129)
5.  Once the HSI is hot, the trial for ignition begins with the 
 
opening of the gas valve.
HTR: IGNITION
OUT: 123.9F(129)
6.  If the SMART SYSTEM control does not sense flame, then 
     it will lock out.
HTR: POSTPURGE, PREPURGE
OUT: 123.9F(129)
7. If the SMART SYSTEM control senses flame, 
   it will fire the burner to maintain the set point.  The 
     stages will fire as required to hold the actual temperature at       
       the set point.  If the boiler lights due to a space heating call for  
   heat, and the ramp delay function is active (default is 
    disabled), the stages will be held to a series of increasing 
     limits after the burner has lit.
HTR: RUN STG: 1
OUT: 124.8F(129)
8.  If the space heating call for heat is active, and the DHW 
thermostat closes, the control will turn on the DHW pump, 
wait 2 seconds, and then turn off the boiler pump.  This will 
divert the hot water away from the heating zone(s) and send 
it to the DHW tank instead.  The control will then fire the 
stages to maintain the outlet temperature to the DHW boiler 
set point.
HTR: DHW STG 123
OUT: 177.8(180)