Fig. 11. Example of alarm hysteresis 
The “normal” and “alarm” states as defined by the attribute "Alarm Hysteresis" are 
the determined using the appropriate values in the formula given above: 
 
Range = [10
-2
 to (Max1 -Min1)] = [0.01 to 2] 
 
Table 7 lists the resulting alarm conditions for the chosen hysteresis value of 0.05: 
 
Table 7. Alarm conditions for alarm hysteresis 
 
limit 
normal to alarm condition  alarm to normal condition 
Max 1 
4.00 
4.00 - 0.05 = 3.95 
Max 2 
5.00 
5.00 - 0.05 = 4.95 
Min 1 
2.00 
2.00 + 0.05 = 2.05 
Min 2 
0.5 
0.5 + 0.05 = 0.55 
 
 
Trend Hysteresis 
 
Trend hysteresis (V1.5.x) 
The attribute "Trend Hysteresis" is available for the trend functions “Local Trend 
Data” and “Trend Setup Data”. The attribute "Trend Hysteresis" prevents new 
values from being written to the trend buffer unless the datapoint value changes 
(positively or negatively) at more than the specified trend hysteresis. The minimum 
hysteresis value is 10
-a
 (a = number of decimal places set in the attribute 
"Engineering Unit"). The CARE default value (i.e. 1% of actual value and no less 
than 0.2) for this attribute is 0. Access to "Trend Hysteresis" is also possible via 
RIA/WIA.  
 
 
This value can be edited from an operator interface (XI581 (not with XCL5010, 
Excel 100C), XI582, XL-Online, or Excel 50 MMI) via the B port (XC5010C/XC6010) 
or the serial port, the system bus (XBS 1.3.3 and higher and XFI 1.6.1 and higher) 
and CARE RIA/WIA statements. The password level for this attribute is determined 
by the attribute "Access" (default initialization value in CARE is 0). 
 
 
Fig. 12. Example of the attribute "Trend Hysteresis"