Honeywell R0512 Manuel D’Utilisation

Page de 86
ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
20 
 
The following four limit value attributes exist: 
 
•  Low Warning Limit 
•  Low Alarm Limit 
•  High Warning Limit 
•  High Alarm Limit 
 
Exceeding the limit values generates an alarm. 
 
 
 
Example: 
Monitoring supply air temperature limits (see Fig. 10). 
 
 
Fig. 10. Monitoring supply air temperature limits 
 
 
Hours Run 
 
Display of elapsed hours 
The attribute "Hours Run" returns the total number of hours during which any of the 
stages is in the ON position. However, if more than one stage is in the ON position, 
the "Hours Run" count is not added up, but rather counted only once. Display of the 
elapsed hours run with activated hours run logging (see also "Hours Run Log" on 
page 20). 
 
NOTE: 
If the attribute "Active State" of the point is 0, then the OFF position is 
also counted. 
 
 
Hours Run Log 
 
Hours run log 
An hours run log can be carried out for digital datapoints (physical and pseudo) and 
for flexible datapoints, e.g. logging the hours run by a heating circuit pump. This 
requires the decision: hours run log = Yes/No to be made in the attribute "Hours 
Run Log". The accumulated hours run are displayed in the attribute “Hours Run”. 
Hours run are logged with a sample rate of 1 minute. 
 
 
Hours Since Serviced 
Display hours run since last maintenance  The elapsed hours run since the last maintenance work are totaled in the attribute 
"Last Maintained". If, for example, the maintenance alarm is 500 hours, and a pump 
has already been running for 120 hours, then the entry in the attribute “Last