Regency IG35 Gas Inbuilt Fireplace
INSTALLATION
IMPORTANT 
MESSAGE
The Regency Gas Fireplace must be installed 
in accordance with these instructions. Carefully 
read all the instructions in this manual fi rst.  
Note:  Failure to follow these instructions 
could cause a malfunction of the 
heater which could result in death, 
serious bodily injury, and/or prop-
erty damage.  Failure to follow these 
instructions may also void your fi re 
insurance and/or warranty.  
FOR YOUR SAFETY
This appliance requires air for proper combus-
tion.  Always provide adequate combustion and 
ventilation air. Follow instructions and informa-
tion in the current AS5601-2004, NZS 5261 
or local codes.  Consult the "authority having 
jurisdiction" to determine the need for a permit 
prior to starting the installation.
BEFORE YOU START
Installation is to be carried out ONLY by an 
authorised person.
1)  The appliance shall be  installed in accord-
ance with the manufacturer's installation 
instructions, local gas fi tting  regulations, 
municipal building codes, water supply 
regulations, electrical wiring regulations, 
with AS5601-2004. (AGA gas installation 
code) NZS 5261(New Zealand)
2)  Installation and repair should be done 
ONLY by an authorised person.  
3)  The  appliance should be inspected before 
use and at least annually by an authorised 
service person. More frequent cleaning may 
be required due to excessive lint from carpet-
ing, bedding material, etc.  It is imperative 
that control compartments, burners and 
circulating air passageways of the appliance 
be kept clean and free from excessive lint 
from carpeting.
4)  See general construction and assembly 
instructions. This appliance may only be in-
stalled in a fl ued, non-combustible fi replace. 
The appliance and fl ue should be enclosed 
when installed or passing through a living 
area, where children may come in contact 
with it.
 
This appliance can also be installed into the 
approved Zero Clearance Kit #486-900 in a 
combustible situation.
5)  Always connect this space heater to a chim-
ney and fl ue to the outside of the building 
envelope. Never fl ue to another room.  Make 
sure that the fl ue is properly sized and is 
of adequate height to provide the proper 
draft.  
6) Inspect the fl ueing system annually for 
blockage and any signs of deterioration.   
7)  Any safety glass removed for servicing 
must be replaced prior to operating the ap-
pliance.  
8)  To prevent  injury, do not allow anyone who 
is unfamiliar with the operation to use the 
fi replace.  
MATERIALS REQUIRED
A 240 Volt AC power cord is hooked up to the 
unit. Plug 3 wire cord into a suitable receptacle. 
Do not cut the ground terminal off under any 
circumstances.
When connected with 240 volts, the appliance 
must be electrically grounded in accordance 
with local codes.
This unit is polarity sensitive and will not oper-
ate if polarity is incorrect.
INSTALLATION 
CHECKLIST
The Regency Gas Insert is installed as listed 
below. 
1)  Unit Location - refer to "Clearances to 
Combustibles" section.
2)  Make the gas connections. Refer to "Gas 
Connections" section. 
3) Install 
the 
fl ue or liner to the fl ue collar. Refer 
to "Flueing" section.
4)  Slide the unit into the fi replace.
5)  Test gas pressure, refer to "Gas Pipe Pres-
sure Testing" section. Check aeration, refer 
to "Aeration Settings" section.
6) Test for fl ue spillage, refer to "Test for Flue 
Spillage" section.
7)  Install the optional brick panels. Refer to 
"Optional Brick Panels" section.
8)  Install the log set. Refer to "Log Set instal-
lation" section.
9)  Assemble and install the faceplate and trim 
and louvres. Refer to "Faceplate, Trim & 
Louvre" section.
10) Optional Premium Flush Front installation. 
Refer to "Premium Flush Front Installation" 
section.
11Final check: Before leaving this unit with the 
customer, the installer must ensure that the 
appliance is fi ring correctly. This includes:
 
a)  Clocking the appliance  to ensure the 
correct fi ring rate.
 
b)  Adjusting the primary air, if required, 
to ensure that the fl ame does not car-
bon.
 
c)  Ensuring that the appliance is fl ueing 
correctly. Refer to "Test for Flue Spillage" 
section.
9)  Installer must mechanically attach the sup-
plied label to the inside of the fi rebox of the 
fi replace into which the gas fi replace insert 
is installed.
"WARNING: This fi replace has been converted 
for use with a gas fi replace insert only and 
cannot be used for burning wood or solid fuels 
unless all original parts have been replaced, 
and the fi replace re-approved by the authority 
having jurisdiction."