Regency IG35 Gas Inbuilt Fireplace
TEST FOR FLUE 
SPILLAGE
A " spillage" test must be made before the 
installed unit is left with the customer. Follow 
the procedure below:
1)  Start all exhaust fans in the home and then 
close all external doors and windows in the 
house.
2)  Light the unit and set controls to maximum. 
Turn fan off.
3)  After fi ve minutes, test that there is a “pull” on 
the fl ue by placing a smoke match, cigarette 
or similar device which gives off smoke, in 
both sides of the unit. See diagram 1.
 
AERATION SETTINGS
The burner aeration is factory set but may need 
adjusting due to either the local gas supply, air 
supply or altitude. This adjustment is performed 
by the installer.  (Close the aeration for a more 
yellow  fl ame, or open it to make the fl ame 
bluer). 
 
NG: 
15mm fully open
 
LPG: 
15mm fully open
 
ULPG: 
15mm fully open
Note:    Any damage due to carboning result-
ing from improperly setting the aera-
tion controls is NOT covered under 
warranty.
Diagram 1
For wind turbulent sites, a wind cap may rem-
edy the problem. These caps are not included 
with the standard fl ue kit and will need to be  
purchased separately.
Side
brick
panel
Back
brick
panel
Brick
R etaining
C lip
Screw
OPTIONAL 
BRICK PANEL
1)  Unwrap the brick panels from the protective 
wrapping.
2)  Remove the glass front and log set if  already 
installed.
3)  Place the rear brick panel fl at against the 
back of the unit, by carefully slipping it be-
tween the back wall of the fi rebox and the 
rear log tray.
4)  Remove the screw on the inside top left and 
right side of the fi rebox.
5)  Slide the left and right side brick panels in 
place and secure using the brick retaining 
clips provided and the screws removed in 
step 4 as shown in the diagram below.
INSTALLATION
The smoke should be drawn into the unit. If the 
smoke is still not drawn into the spill tube, turn 
the unit off and check for the cause of the lack 
of draft. If necessary, rectify. 
Left Side
of Firebox
R em ove
screw
IG35-NG: For 0 to 610 meters altitude
IG35-LPG: For 0 to 610 meters altitude
IG35-ULPG: For 0 to 610 meters altitude
Burner Inlet Orifi ce Sizes:
                  NG 
       LPG        ULPG
Burner    #33 
       #51          #53
 
            
Max. Input 
 NG 
33.5 
mj 
 LPG 
34 
mj
 ULPG 
28 
mj
Min. Input 
 NG 
19.6 
mj
 LPG 
18.5 
mj
 ULPG 
14 
mj
  
Supply Pressure   
 NG 
1.13 
kPa
 LPG 
2.75 
kPa
 ULPG 
2.75 
kPa
Manifold Pressure
 NG 
0.87 
kPa
 LPG 
2.61 
kPa
 ULPG 
2.61 
kPa
Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan,
 
            150/89 CFM.
Log Set: Ceramic fi ber, 7 per set.
Aeration Setting
NG       15mm fully open 
LPG        15mm fully open
ULPG      15mm fully open
 
        
System Data