MALFUNCTION POSSIBLE 
CAUSE SOLUTION 
 
Compressor will not start -  
1.  Service cord unplugged 
1.  Plug in service cord 
no hum 
2.  Fuse blown or removed 
2.  Replace fuse 
 
3.  Overload tripped 
3.  Determine reasons and correct 
 
4.  Control stuck open 
4.  Repair or replace 
 
5.  Wiring incorrect 
5.  Check wiring against the diagram 
 
Compressor will not start - 
1.  Improperly wired 
1.  Check wiring against the diagram 
hums but trips on overload 
2.  Low voltage to unit 
2.  Determine reason and correct 
protector 
3.  Starting capacitor defective 
3.  Determine reason and replace 
 
4.  Relay failing to close 
4.  Determine reason, correct or replace 
 
 
Compressor starts and runs, 
1.  Low voltage to unit 
1.  Determine reason and correct 
but short cycles on overload 
2.  Overload defective 
2.  Check current, replace overload protector 
protector 
3.  Excessive head pressure 
3.  Check ventilation or restriction in  
 
 
     refrigeration system 
 
4.  Compressor hot-return gas hot 
4.  Check refrigerant charge, fix leak if necessary 
  
Compressor operates long 
1.  Short of refrigerant 
1.  Fix leak, add charge 
or continuously 
2.  Control contact stuck 
2.  Repair or replace 
 
3.  Evaporator coil iced 
3.  Determine cause, defrost manually 
 
4.  Restriction in refrigeration system  4.  Determine location and remove restriction  
 
5.  Dirty condenser 
5.  Clean condenser 
 
Compressor runs fine, but 
1.  Overload protector 
1.  Check wiring diagram 
short cycles 
2.  Cold control 
2.  Differential too close - widen 
 
3.  Overcharge 
3.  Reduce charge 
 
4.  Air in system 
4.  Purge and recharge 
 
5.  Undercharge 
5.  Fix leak, add refrigerant 
 
Starting capacitor open, 
1. Relay contacts stuck 
1.  Clean contacts or replace relay 
shorted or blown 
2.  Low voltage to unit 
2.  Determine reason and correct 
 
3.  Improper relay 
3.  Replace 
 
 
 
Relay defective or burned out 
1.  Incorrect relay 
1.  Check and replace 
 
2.  Voltage too high or too low 
2.  Determine reason and correct 
 
Refrigerated space too warm 
1.  Control setting too high 
1.  Reset control 
 
2.  Refrigerant overcharge 
2.  Purge refrigerant 
 
3.  Dirty condenser 
3.  Clean condenser 
 
4.  Evaporator coil iced 
4.  Determine reason and defrost 
 
5.  Not operating 
5.  Determine reason, replace if necessary 
 
Standard temperature system 
1.  Control setting is too low 
1.  Reset the control 
freezes the product 
2.  Control points stuck 
2.  Replace the control 
 
Objectionable noise 
1.  Fan blade hitting fan shroud 
1.  Reform or cut away small section of shroud 
 
2.  Tubing rattle 
2.  Locate and reform 
 
3.  Vibrating fan blade 
3.  Replace fan blade 
 
4.  Condenser fan motor rattles 
4.  Check motor bracket mounting, tighten 
 
5.  General vibration 
5.  Compressor suspension bolts not loosened
 
 
 
on applicable models - loosen them 
 
6.  Worn fan motor bearings 
6.  Replace fan motor 
 
Pan Area 
1.  No cooling 
1.  Make sure switch is in the "on" position 
 
2.  Too cold 
2.  Adjust temperature control - see instructions 
 
 
 
under pan area 
 
3.  Too warm 
3.  Adjust temperature control - see instructions 
 
 
 
under pan area