Emerson 510 Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Installation, Operation and Maintenance Manual
4
IO-70103 Rev 0, 1/2013
Surge Protective Devices
ELECTRICAL CONNECTIONS
All electrical connections should be installed by a qualified
(licensed) electrician only. All wiring must comply with the
National Electrical Code (NEC) and applicable local
codes.
(licensed) electrician only. All wiring must comply with the
National Electrical Code (NEC) and applicable local
codes.
VERIFY THAT ALL POWER CIRCUITS ARE
DE-ENERGIZED AND LOCKED OUT BEFORE MAKING
ELECTRICAL CONNECTIONS.
Voltage Ratings and Power Source Configurations
Before making connections to the unit, verify that the unit
model number and nameplate voltage rating are
appropriate for connection to the intended power source.
See the chart on page 3 for voltage rating applications
with typical power source configurations.
model number and nameplate voltage rating are
appropriate for connection to the intended power source.
See the chart on page 3 for voltage rating applications
with typical power source configurations.
Wire Connections
With parallel connection, the size of
the wiring to the SPD unit is independent of the protected
circuit s ampacity. NEC Article 285-21(B) requires surge
suppressor connecting conductors to be at least #14
copper or #12 aluminum. To reduce the wiring impedance
to surge currents, it is recommended that the phase,
neutral (if required), and ground conductors are twisted
together and routed in the same raceway (conduit). Avoid
any sharp bends in the conductors.
circuit s ampacity. NEC Article 285-21(B) requires surge
suppressor connecting conductors to be at least #14
copper or #12 aluminum. To reduce the wiring impedance
to surge currents, it is recommended that the phase,
neutral (if required), and ground conductors are twisted
together and routed in the same raceway (conduit). Avoid
any sharp bends in the conductors.
Overcurrent Protection
The SPD unit conducts
practically no current under normal operation and only
conducts very short duration transient surge currents.
conducts very short duration transient surge currents.
NEC Considerations - The following is from the National
Electric Code 2008 Edition.
Electric Code 2008 Edition.
NEC 285.21 Connections
NEC 285.23 Type 1 SPD s. Shall be installed in
accordance with 285.35(A) and (B).
accordance with 285.35(A) and (B).
(A) Installation. Type 1 SPD s shall be installed as
follows:
follows:
(1) Type 1 SPD s shall be permitted to be connected to
the supply side of the service disconnect as
permitted in
the supply side of the service disconnect as
permitted in
230.82(4) or
(2) Type 1 SPD s shall be permitted to be
connected in Type 2 locations as specified in 285.24.
connected in Type 2 locations as specified in 285.24.
(B) At the service. When installed at the services, the
grounding conductor of a Type 1 SPD shall be connected
to one of the following:
grounding conductor of a Type 1 SPD shall be connected
to one of the following:
(1) Grounded service conductor
(2) Grounded electrode conductor
(3) Grounding electrode for service
(4)Equipment grounding terminal in the service equipment
Voltage Protection Ratings
To obtain the voltage
protection ratings (VPR s), as obtained by Underwriters
Laboratory, Incorporated, in accordance with the Standard
for Safety, Surge Protective Devices (SPD s), Standard 1449,
Third Edition, released (2009), marked on this product, the
wire size listed for each product must be utilized to connect
the unit to your facilities
Laboratory, Incorporated, in accordance with the Standard
for Safety, Surge Protective Devices (SPD s), Standard 1449,
Third Edition, released (2009), marked on this product, the
wire size listed for each product must be utilized to connect
the unit to your facilities
power grid. Connections made with
conductors other than the wire size listed may result in
different VPR s.
different VPR s.
Circuit Ampacity Limitations
Representative samples of
these products have been investigated by Underwriters
Laboratories, Incorporated to withstand, without exposing
live circuits or components at system voltages and fault
currents up to 200,000 AIC, as described in the Standard for
Safety, Surge Protective Devices (SPD s), Standard 1449,
Third Edition, released (2009).
Laboratories, Incorporated to withstand, without exposing
live circuits or components at system voltages and fault
currents up to 200,000 AIC, as described in the Standard for
Safety, Surge Protective Devices (SPD s), Standard 1449,
Third Edition, released (2009).
System Grounding and Bonding
The performance and
safety of any SPD system is dependent on proper grounding
and bonding. Grounding is required for safety. Correct
implementation also enhances equipment performance.
Incorrect grounding can reduce or impede the SPD s
operation.
and bonding. Grounding is required for safety. Correct
implementation also enhances equipment performance.
Incorrect grounding can reduce or impede the SPD s
operation.
All electrical circuits to the SPD must include an equipment-
grounding conductor as
required by the NEC and local
codes.
required by the NEC and local
codes.
UNGROUNDED POWER SYSTEMS ARE INHERENTLY
UNSTABLE AND CAN PRODUCE EXCESSIVELY HIGH
LINE-TO- GROUND VOLTAGES DURING CERTAIN FAULT
CONDITIONS. DURING THESE FAULT CONDITIONS ANY
ELECTRICAL EQUIPMENT, INCLUDING AN SPD, MAY BE
SUBJECTED TO VOLTAGES WHICH EXCEED THEIR
DESIGNED RATINGS. THIS INFORMATION IS BEING
PROVIDED TO THE USER SO THAT AN INFORMED
DECISION CAN BE MADE BEFORE INSTALLING ANY
ELECTRICAL EQUIPMENT ON AN UNGROUNDED
POWER SYSTEM. CONTACT FACTORY FOR
UNGROUNDED APPLICATIONS.
UNSTABLE AND CAN PRODUCE EXCESSIVELY HIGH
LINE-TO- GROUND VOLTAGES DURING CERTAIN FAULT
CONDITIONS. DURING THESE FAULT CONDITIONS ANY
ELECTRICAL EQUIPMENT, INCLUDING AN SPD, MAY BE
SUBJECTED TO VOLTAGES WHICH EXCEED THEIR
DESIGNED RATINGS. THIS INFORMATION IS BEING
PROVIDED TO THE USER SO THAT AN INFORMED
DECISION CAN BE MADE BEFORE INSTALLING ANY
ELECTRICAL EQUIPMENT ON AN UNGROUNDED
POWER SYSTEM. CONTACT FACTORY FOR
UNGROUNDED APPLICATIONS.
An insulated grounding conductor is required in addition to any
metallic raceway, which may be used as a grounding conductor.
For parallel-connected SPDs, the grounding conductor should
be the same wire size as the associated power
conductors.
metallic raceway, which may be used as a grounding conductor.
For parallel-connected SPDs, the grounding conductor should
be the same wire size as the associated power
conductors.