Surge Protective Devices
 
Installation, Operation and Maintenance Manual
 
2
 
IO-70103 Rev 0, 1/2013
 
 
 
UNPACKING AND INSTALLATION
 
 
Unpacking and Preliminary Inspection
 
1. Inspect   the   shipping   crate(s)   for   damage   or   
signs   of mishandling before unpacking the unit.
 
2. Remove  any  securing  bands  and  cardboard  packing  
and inspect the unit for any obvious shipping damages.
 
3. If any damage as a result of shipping is observed, 
immediately file a claim with the shipping agency and 
forward a copy to your local Emerson Network Power 
Surge Protection Sales Representative.
     
Handling Considerations
 
Larger units are bolted to a shipping pallet to facilitate 
handling by forklift or  pallet jack. Check  the size and 
weight.   Refer  to the cabinet data furnished with the unit.
     
Storage
 
The   unit   should   be   stored   in   a   clean,   dry  
environment. Storage  temperature  range  is  -55ºC  (-67ºF)  
to  +85ºC (+185ºF).   Care should be taken to avoid 
condensation. All packing  and  shipping  materials  should  
be  left  intact  until the unit is ready for final installation. If 
the unit has been stored for an extended period of time, the 
unit should be cleaned  and  carefully  inspected  before 
placing  into  service. 
LOCATION CONSIDERATIONS 
 
For optimum transient surge protection, coordinated surge 
suppression should be applied at the service entrance and 
all other electrical connections to the building (telephone, 
CATV, etc.), at known surge generating loads within the 
building (large motors, arc welders, switched capacitors, 
etc.), as well as at sensitive electronic loads (such as 
computers, electronic appliances, solid state motor drives, 
etc.). For interconnected electronic loads (such as by way of 
data cabling), transient surge suppression should also be 
applied to the interconnecting wiring (data cables).
 
Environment 
 
Unit is designed for operation indoors in 
ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) 
with a relative humidity of 0% to 95% (non-condensing).
 
The unit is provided in an industrial use enclosure, which is 
dust-tight and drip-tight and should not be installed in areas 
with excessive dust, corrosive vapors, flammable materials 
or explosive atmospheres.
 
Audible  Noise 
 
The  audible  noise  of  the  unit  is  less 
than 40 dB at 5 feet, which allows its placement within 
almost any room if desired.
 
Service Clearances 
 
Service clearance is needed for units 
with hinged doors on the front that are capable of being 
opened. Thirty-six inches (36 in/914 mm) minimum is 
recommended.
 
Mounting 
 
Unit is intended to be wall mounted. Refer to 
installation instructions for mounting dimensions and weight.
 
Warnings Defined 
  
Danger: Indicates an imminently 
hazardous situation that, if not 
avoided, will result in death or 
serious    injury.    This    signal   
word is  to  be  limited  to  the  
most extreme situations.
 
Warning: Indicates a potentially 
hazardous situation that, if not 
avoided, could result in death or 
serious injury.
 
Caution: Indicates a potentially 
hazardous situation that, if not 
avoided, may result in minor or 
moderate injury. It may also be 
used to alert against unsafe 
practices.