7.3  Power Range:1000 VA (19” Rack-mount model, LV, 1U & 2U)
General
Rated power:
1000 VA at power factor 0.7
Technology:
On-line, double conversion topology with automatic
bypass
Input
Phase:
Single phase with ground
Bypass Voltage: 
96VAC- 138VAC (user selectable)
Input Voltage range: 
80VAC- 144VAC
Frequency:
50/60 Hz Auto selection
Frequency window from main supply:
45-65 Hz
Synchronization window:
± 3Hz
Input current:
1000 VA 8.2A
Input Power factor:
0.97
Output
Output Voltage:
100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full
linear load:
Frequency regulation:
± 0.25 Hz (battery or free running mode)
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 %
linear load:
Overload capacity:
100-125% 1 min, 125-150% 10 sec
Efficiency:
greater than 86%
Environmental
Ambient temperature:
+0 °C to +40 °C
Recommended temperature: +15 °C to +25 °C
Storage temperature:
-15 °C to +50 °C
Cooling:
Forced air-cooling
Humidity:
0-95%, non-condensing
Audible noise:
< 45 db normal and battery mode (1000 ~1200 VA)