7.4  Power Range 1000-1200 VA (HV)
General
Rated power:
1000 VA, 1200 VA at power factor 0.7
Technology:
On-line, double conversion topology with automatic
bypass
Input
Phase:
Single phase with ground
Bypass Voltage: 
184VAC-265VAC (user selectable)
Input Voltage range: 
160VAC-276VAC
Frequency:
50/60 Hz Auto selection
Frequency window from main supply:
45-65 Hz
Synchronization window:
± 2.5Hz
Input current:
1000 VA 4A, 1200 VA 5.2A
Input Power factor:
0.97
Output
Output Voltage:
208/220/230/240 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full
linear load
Frequency regulation:
± 0.25 Hz (battery or free running mode)
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 %
linear load
Overload capacity:
100-125% 1 min, 125-150% 10 sec
Efficiency: