Emerson MODBUS 485 Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Modbus 485 and Modbus IP Protocols - UPS Systems
169
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
DC Bus Low Fault
10074
—
1
Active on Alarm
Output
System Shutdown - EPO
System Shutdown - EPO
10085
—
1
Active on Alarm
System Shutdown - REPO
10086
—
1
Active on Alarm
System Output Low Power Factor
10088
—
1
Active on Alarm
Output Amp Over User Limit-Phs A
10089
—
1
Active on Alarm
Output Amp Over User Limit-Phs B
10090
—
1
Active on Alarm
Output Amp Over User Limit-Phs C
10091
—
1
Active on Alarm
System Output Fault
10092
—
1
Active on Alarm
Output Of/Uf
10093
—
1
Active on Alarm
Inverter
Inverter Failure
Inverter Failure
10104
—
1
Active on Alarm
Inverter Overload Phase A
10105
—
1
Active on Alarm
Inverter Overload Phase B
10106
—
1
Active on Alarm
Inverter Overload Phase C
10107
—
1
Active on Alarm
Inverter Inhibit - External
10108
—
1
Active on Alarm
Inverter Shutdown - Overload
10109
—
1
Active on Alarm
Inverter Static Switch SCR Short
10110
—
1
Active on Alarm
Environment
Inlet Air Over Temperature
Inlet Air Over Temperature
10121
—
1
Active on Alarm
Outlet Air Overtemperature Limit
10122
—
1
Active on Alarm
Equipment Temperature Sensor Fail
10123
—
1
Active on Alarm
External Input Signals
Input Contact 01
Input Contact 01
10134
—
1
Active on Alarm
Input Contact 02
10135
—
1
Active on Alarm
Input Contact 03
10136
—
1
Active on Alarm
Input Contact 04
10137
—
1
Active on Alarm
Input Contact 05
10138
—
1
Active on Alarm
Input Contact 06
10139
—
1
Active on Alarm
Input Contact 07
10140
—
1
Active on Alarm
Input Contact 08
10141
—
1
Active on Alarm
Input Contact 09
10142
—
1
Active on Alarm
Input Contact 10
10143
—
1
Active on Alarm
Input Contact 11
10144
—
1
Active on Alarm
Input Contact 12
10145
—
1
Active on Alarm
Input Contact 13
10146
—
1
Active on Alarm
Input Contact 14
10147
—
1
Active on Alarm
Input Contact 15
10148
—
1
Active on Alarm
Input Contact 16
10149
—
1
Active on Alarm
Rectifier
Rectifier Failure
Rectifier Failure
10160
—
1
Active on Alarm
Vdc Backfeed
10162
—
1
Active on Alarm
Rectifier Configuration Change Request
10163
—
1
Active on Alarm
System
System Fan Failure - Redundant
System Fan Failure - Redundant
10174
—
1
Active on Alarm
Multiple Fan Failure
10175
—
1
Active on Alarm
Internal Communications Failure
10176
—
1
Active on Alarm
Table 58
Liebert NXL
™
- 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description
Status
Coil
Number
of Bits
Notes / Units