Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
170
UPS Output on Bypass
10177
1
Active on Alarm
Output Load on Maint. Bypass
10178
1
Active on Alarm
Backfeed Breaker Open
10179
1
Active on Alarm
Auto Restart In Progress
10180
1
Active on Alarm
Power Supply Failure
10181
1
Active on Alarm
Auto Restart Inhibited - Ext
10183
1
Active on Alarm
Automatic Restart Failed
10184
1
Active on Alarm
Main Controller Fault
10185
1
Active on Alarm
Fuse Failure
10186
1
Active on Alarm
System Controller Error
10187
1
Active on Alarm
System Breaker(s) Open Failure
10188
1
Active on Alarm
System Breaker(s) Close Failure
10189
1
Active on Alarm
Input Filter Cycle Lock
10190
1
Active on Alarm
EMO Shutdown
10191
1
Active on Alarm
Service Code Active
10192
1
Active on Alarm
LBS Active
10193
1
Active on Alarm
LBS Inhibited
10194
1
Active on Alarm
Regeneration Active
10195
1
Active on Alarm
Regeneration Operation Terminated
10196
1
Active on Alarm
Regeneration Operation Failure
10197
1
Active on Alarm
Leading Power Factor
10198
1
Active on Alarm
Controls Reset Required
10199
1
Active on Alarm
MultiModule
Loss of Redundancy
10212
1
Active on Alarm
MMS Overload
10215
1
Active on Alarm
MMS On Battery
10216
1
Active on Alarm
MMS Module Alarm Active
10218
1
Active on Alarm
Program Input Signals
Program Input Contact 01
10229
1
Active on Alarm
Program Input Contact 02
10230
1
Active on Alarm
Program Input Contact 03
10231
1
Active on Alarm
Program Input Contact 04
10232
1
Active on Alarm
Program Input Contact 05
10233
1
Active on Alarm
Program Input Contact 06
10234
1
Active on Alarm
Program Input Contact 07
10235
1
Active on Alarm
Program Input Contact 08
10236
1
Active on Alarm
Program Input Contact 09
10237
1
Active on Alarm
Program Input Contact 10
10238
1
Active on Alarm
Program Input Contact 11
10239
1
Active on Alarm
Program Input Contact 12
10240
1
Active on Alarm
Intelligent Paralleling
IP Inhibit
10251
1
Active on Alarm
ECO Mode
ECO Mode Active
10262
1
Active on Alarm
ECO Mode Suspended
10263
1
Active on Alarm
Excess ECO Suspends
10264
1
Active on Alarm
Table 58
Liebert NXL
 - 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description
Status
Coil
Number
of Bits
Notes / Units