Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
182
Table 60
Liebert NXL
 - 50Hz, CE version (Models 48 and 49) - Glossary
Data Label
Data Description
Auto Restart In Progress
Auto restart is in progress
Auto Restart Inhibited - Ext
Auto restart inhibited due to an external signal
Auto Retransfer Time Remaining
Time remaining before an inverter overload or inverter fault can be cleared and auto 
retransfer from the bypass to the inverter can take place
Automatic Restart Failed
Automatic restart failed
Backfeed Breaker Open
The backfeed breaker is in the open position
Backfeed Breaker
Backfeed breaker
Battery - External Monitor 1
External battery monitor 1 - battery maintenance required
Battery - External Monitor 2
External battery monitor 2 - battery maintenance required
Battery Amp-Hours Consumed This 
Discharge
Battery amp-hours withdrawn this discharge.
Battery Amp-Hours Consumed
Cumulative battery amp-hours withdrawn over the life of the battery
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Automatic Test Inhibited
Automatic (scheduled) battery tests are inhibited
Battery Capacity Low
Battery capacity is low
Battery Cell Count - Lead Acid
Battery cell count - lead acid
Battery Cell Count-Nickel Cadmium
Battery cell count - nickel cadmium
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Circuit Breaker 5 Open
Battery circuit breaker 5 is open
Battery Circuit Breaker 6 Open
Battery circuit breaker 6 is open
Battery Discharge Power
Instantaneous battery power while discharging
Battery Discharge Time
The time on battery operation for this discharge
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage level.
Battery Fuse Fault
One or more battery fuse faults has occurred.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Last Discharge Date
The date and time of the last battery discharge
Battery Low Shutdown
The battery voltage has dropped to the End of Discharge value.
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Over Temperature Limit
A battery temperature sensor is reporting a value above a predetermined limit.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Over Voltage
The system has detected that the battery voltage has exceeded a predetermined 
limit.
Battery Percentage Charge
The percentage of battery charge
Battery SCR Status
The status of the battery SCR.
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature Imbalance
Excessive temperature differences between battery sensors detected
Battery Temperature Sensor Fault
A battery temperature sensor fault has been detected
Battery Test Failed
Battery test failed
Battery Test Manually Stopped
The battery test was manually stopped prior to completion
Battery Test Passed
Battery test passed