Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
184
Controls Reset Required
A controls reset is required due to one or more critical settings changing
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a 
positive value. In discharging mode, the current will be a negative value
DC Bus Low Fault
The DC Bus voltage has reached a critical low level.
DC Bus Qualification Status
dc bus qualification status
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at the battery 
input
ECO Mode Active
Conditions for Activation or Automatic Reactivation have been satisfied.
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
ECO Mode Suspended
ECO Mode session is suspended.
EMO Shutdown
An Emergency Module Off command has been detected.
Equipment Temperature Sensor Fail
One or more temperature sensors report a temperature outside of the range of 
expected operation.
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto 
Suspensions setting.
Fuse Failure
A summary event indicating one or more fuse failures
Inlet Air Over Temperature
The inlet air exceeds the maximum temperature threshold
Inlet Air Temperature
The temperature of the inlet air
Input Breaker
Input breaker
Input Contact 01
The external input contact 1
Input Contact 02
The external input contact 2
Input Contact 03
The external input contact 3
Input Contact 04
The external input contact 4
Input Contact 05
The external input contact 5
Input Contact 06
The external input contact 6
Input Contact 07
The external input contact 7
Input Contact 08
The external input contact 8
Input Contact 09
The external input contact 9
Input Contact 10
The external input contact 10
Input Contact 11
The external input contact 11
Input Contact 12
The external input contact 12
Input Contact 13
The external input contact 13
Input Contact 14
The external input contact 14
Input Contact 15
The external input contact 15
Input Contact 16
The external input contact 16
Input Filter Cycle Lock
The input filter disconnect is open due to exceeding the maximum number of cycles.
Input Isolation Transformer
Input isolation transformer
Input Qualification Status
Input qualification status
Intelligent Parallel Maximum Time in 
Standby
The maximum time a module can be in standby mode due to Intelligent Paralleling.
Intelligent Parallel Minimum 
Redundancy
This is the minimum Number of Redundant Modules that the system will allow before 
bringing one or more modules back to normal operation and terminating Intelligent 
Paralleling.
Intelligent Parallel Operation State
This setting is used to enable or disable Intelligent Paralleling.
Internal Bypass Breaker
Internal bypass breaker
Table 60
Liebert NXL
 - 50Hz, CE version (Models 48 and 49) - Glossary
Data Label
Data Description