Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
241
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Compressor Pump Down Issue 
- Event Type
MultiState_Value
207
5396_1_2
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Compressor Short Cycle - 
Event Control
MultiState_Value
208
5397_1_2
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Compressor Short Cycle - 
Event Type
MultiState_Value
209
5398_1_2
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Compressor Thermal Overload 
- Event Control
MultiState_Value
210
5320_1_2
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Compressor Thermal Overload 
- Event Type
MultiState_Value
211
5321_1_2
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Dig Scroll Comp Discharge 
Over Temp - Event Ctrl
MultiState_Value
212
5399_1_2
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Dig Scroll Comp Discharge 
Over Temp - Event Type
MultiState_Value
213
5400_1_2
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
System Event Configuration - Air
Ext Air Sensor A Event Control
MultiState_Value
224
5401_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Return Air Sensor Event 
Control
MultiState_Value
225
5402_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Ext Air Sensor A High Humidity 
- Event Control
MultiState_Value
226
5403_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Ext Air Sensor A High Humidity 
- Event Type
MultiState_Value
227
5404_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Ext Air Sensor A Low Humidity - 
Event Control
MultiState_Value
228
5405_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Ext Air Sensor A Low Humidity - 
Event Type
MultiState_Value
229
5406_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Ext Air Sensor A Over Temp - 
Event Control
MultiState_Value
230
4602_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Ext Air Sensor A Over Temp - 
Event Type
MultiState_Value
231
4603_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Ext Air Sensor A Under Temp - 
Event Control
MultiState_Value
232
4609_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Ext Air Sensor A Under Temp - 
Event Type
MultiState_Value
233
4610_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
High Return Humidity - Event 
Control
MultiState_Value
234
5137_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
High Return Humidity - Event 
Type
MultiState_Value
235
5138_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Low Return Humidity - Event 
Control
MultiState_Value
236
5139_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Table 80
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Multistate Data (continued)
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra 
Notes