Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
242
Low Return Humidity - Event 
Type
MultiState_Value
237
5140_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Return Air Over Temp - Event 
Control
MultiState_Value
238
5024_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Return Air Over Temp - Event 
Type
MultiState_Value
239
5025_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Return Air Under Temp - Event 
Control
MultiState_Value
240
5407_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Return Air Under Temp - Event 
Type
MultiState_Value
241
5408_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Supply Air Over/Under 
Temperature - Event Control
MultiState_Value
242
5587_1_1
RW
1 = disabled
2 = enabled
2, 3, 4, 
5, 6
System Event Configuration - Fan
Fan Hours Exceeded - Event 
Control
MultiState_Value
252
5409_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Fan Hours Exceeded - Event 
Type
MultiState_Value
253
5410_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
Fan Issue - Event Control
MultiState_Value
254
4730_1_1
RW
1 = disabled
2 = enabled
1
Fan Issue - Event Type
MultiState_Value
255
4731_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1
Main Fan Overload - Event 
Control
MultiState_Value
256
5411_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Main Fan Overload - Event 
Type
MultiState_Value
257
5412_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
System Event Configuration - Condenser
Condenser Issue - Event 
Control
MultiState_Value
268
5413_1_1
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Condenser Issue - Event Type
MultiState_Value
269
5414_1_1
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
System Event Configuration - Condenser
Condenser Issue - Event 
Control
MultiState_Value
280
5413_1_2
RW
1 = disabled
2 = enabled
1, 2, 3, 
4, 5, 6
Condenser Issue - Event Type
MultiState_Value
281
5414_1_2
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 
4, 5, 6
System Events
System Event Acknowledge/
Reset
MultiState_Value
292
4717_1
WO
1 = Reset
2 = Acknowledge
1, 2, 3, 
4, 5, 6
Compressors
Compressor Lockout
MultiState_Value
304
5580_1
RW
1 = disabled
2 = enabled
2, 3, 4, 
5, 6
Table 80
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Multistate Data (continued)
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra 
Notes