BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
254
Service Required
Unit requires servicing.
Shutdown - Loss Of Power - Event 
Control
Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list.
Shutdown - Loss Of Power - Event Type
The event type for the [Shutdown - Loss Of Power] event.
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is powered on 
following an unexpected loss of power.  This event remains active for 90 
minutes.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', 
the event will not be annunciated. This implies that the event will not be placed 
in any active event list or in any event history list.
Smoke Detected - Event Type
The event type for the [Smoke Detected] event.
Smoke Detected
Smoke detected.
Standby Units
The number of standby units.
Static Pressure Sensor Issue
The static pressure sensor is disconnected or the signal is out of range.
Static Pressure Sensor Out of Range
Static pressure sensor signal is out of its configured range.
Static Pressure Set Point
Desired static pressure.
Supply Air Over Temp Threshold
Threshold value used in the [Supply Air Over Temperature] event.
Supply Air Over Temperature
Supply air high temperature event.
Supply Air Over/Under Temperature - 
Event Control
Enable/disable the activation of the [Supply Air Over Temperature] and [Supply 
Air Under Temperature] events.
Supply Air Sensor Issue
The air sensor at the outlet of the unit is disconnected or the signal is out of 
range.
Supply Air Temperature Sensor Control
Control mode to be used with the supply air temperature sensor.
Supply Air Temperature Set Point
Desired supply air temperature.
Supply Air Temperature
Air temperature measured at the outlet of the unit.
Supply Air Under Temp Threshold
Threshold value used in the [Supply Air Under Temperature] event.
Supply Air Under Temperature
Supply air low temperature event.
Supply Chilled Water Loss of Flow
Supply chilled water flow is too low.
Supply Chilled Water Over Temp
Chilled water temperature is too high, as indicated by an external input signal.
System Control Mode
System control mode.
System Date and Time
The system date and time
System Event Acknowledge/Reset
Reset and/or acknowledge all events.
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System On/Off Control
Turn system functionality on or off.
System Operating State Reason
The reason the system is in the current operating state.
System Operating State
Current operating state of the system.
System Static Pressure
Static pressure measurement among a group of interconnected units in a single 
system.
System Status
The operating status for the system
Table 82
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Glossary
Data Label