Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
256
Table 83
Liebert CRV
 - Binary Data
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Air Temperature
Supply Air Over Temperature
Binary_Value
1
5015_1
RD
Active on Alarm
Supply Air Under Temperature
Binary_Value
2
5019_1
RD
Active on Alarm
Return Air Over Temperature
Binary_Value
3
5023_1
RD
Active on Alarm
Supply Air Sensor Issue
Binary_Value
4
5026_1
RD
Active on Alarm
Return Air Sensor Issue
Binary_Value
5
5147_1
RD
Active on Alarm
Humidity
High Return Humidity
Binary_Value
16
5034_1
RD
Active on Alarm
Low Return Humidity
Binary_Value
17
5036_1
RD
Active on Alarm
Humidifier Hours Exceeded
Binary_Value
18
5037_1
RD
Active on Alarm
Dehumidifier Hours Exceeded
Binary_Value
19
5038_1
RD
Active on Alarm
Humidifier Under Current
Binary_Value
20
5039_1
RD
Active on Alarm
Humidifier Over Current
Binary_Value
21
5040_1
RD
Active on Alarm
Humidifier Low Water
Binary_Value
22
5041_1
RD
Active on Alarm
Humidifier Cylinder Worn
Binary_Value
23
5042_1
RD
Active on Alarm
Humidifier Issue
Binary_Value
24
5043_1
RD
Active on Alarm
Ext Humidifier Lockout
Binary_Value
25
5044_1
RD
Active on Alarm
Humidifier Control Board Not Detected
Binary_Value
26
5045_1
RD
Active on Alarm
Return Humidity Out Of Proportional Band
Binary_Value
27
5046_1
RD
Active on Alarm
Fans
Loss of Air Flow
Binary_Value
38
5053_1
RD
Active on Alarm
Fan Hours Exceeded
Binary_Value
39
5054_1
RD
Active on Alarm
Top Fan Issue
Binary_Value
40
5055_1
RD
Active on Alarm
Bottom Fan Issue
Binary_Value
41
5056_1
RD
Active on Alarm
Remote Sensors 1
Remote Sensor Issue
Binary_Value
52
5060_1
RD
Active on Alarm
Remote Sensors 2
Remote Sensor Issue
Binary_Value
63
5060_2
RD
Active on Alarm
Remote Sensors 3
Remote Sensor Issue
Binary_Value
74
5060_3
RD
Remote Sensors 4
Remote Sensor Issue
Binary_Value
85
5060_4
RD
Active on Alarm
Remote Sensors 5
Remote Sensor Issue
Binary_Value
96
5060_5
RD
Active on Alarm
Remote Sensors 6
Remote Sensor Issue
Binary_Value
107
5060_6
RD
Active on Alarm
Remote Sensors 7
Remote Sensor Issue
Binary_Value
118
5060_7
RD
Active on Alarm
Remote Sensors 8
Remote Sensor Issue
Binary_Value
129
5060_8
RD
Active on Alarm
Remote Sensors 9
Remote Sensor Issue
Binary_Value
140
5060_9
RD
Active on Alarm