Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
263
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Event Configuration
System Event Acknowledge/Reset 
MultiState_Value
171
4717_1
WO
1 = Reset 
2 = Acknowledge 
Smoke Detected - Event Control 
MultiState_Value
172
4721_1
RW
1 = disabled 
2 = enabled 
Smoke Detected - Event Type 
MultiState_Value
173
4722_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Water Under Floor - Event Control 
MultiState_Value
174
4724_1
RW
1 = disabled 
2 = enabled 
Water Under Floor - Event Type 
MultiState_Value
175
4725_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Customer Input 1 - Event Control MultiState_Value
176
4718_1
RW
1 = disabled 
2 = enabled 
Customer Input 1 - Event Type MultiState_Value
177
4719_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Customer Input 2 - Event Control MultiState_Value
178
5098_1
RW
1 = disabled 
2 = enabled 
Customer Input 2 - Event Type MultiState_Value
179
5099_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Customer Input 3 - Event Control MultiState_Value
180
5100_1
RW
1 = disabled 
2 = enabled 
Customer Input 3 - Event Type MultiState_Value
181
5101_1
RW
1 = Message 
2 = Warning
3 = Alarm
Customer Input 4 - Event Control MultiState_Value
182
5102_1
RW
1 = disabled 
2 = enabled 
Customer Input 4 - Event Type MultiState_Value
183
5103_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Service Required - Event Control 
MultiState_Value
184
4727_1
RW
1 = disabled 
2 = enabled 
Service Required - Event Type 
MultiState_Value
185
4728_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Shutdown - Loss Of Power - Event 
Control 
MultiState_Value
186
4715_1
RW
1 = disabled 
2 = enabled 
Shutdown - Loss Of Power - Event Type 
MultiState_Value
187
4716_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Ext Loss of Flow - Event Control 
MultiState_Value
188
5082_1
RW
1 = disabled 
2 = enabled 
Ext Loss of Flow - Event Type 
MultiState_Value
189
5083_1
RW
1 = Message 
2 = Warning 
3 = Alarm 
Ext Reheat Lockout - Event Control 
MultiState_Value
190
5084_1
RW
1 = disabled 
2 = enabled 
Table 85
Liebert CRV
 - Multistate Data (continued)
Controller
Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes