Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
265
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 86
Liebert CRV
 - Glossary
Data Label
Data Description
Air Temperature Control Sensor 
Sensor from which air temperature measurements will be used for cooling and 
heating control. 
Air Temperature Dead Band 
Value that is divided evenly to form a temperature range above and below [Air 
Temperature Set Point]. If measured air temperature is within this range, no 
heating or cooling will occur. 
Air Temperature Set Point 
Desired air temperature. This set point is dependent upon which sensor is 
selected for control. 
Auto Restart Delay 
If power is lost, the control will delay this amount of time after power is restored 
before restarting the unit. 
BMS Communications Timeout 
Building Management System (or external monitoring system) has not 
communicated with the system within the expected timeframe. 
BMS Timeout Period 
Timeframe within which the Building Management System (or external 
monitoring system) must communicate with the system to avoid a timeout.
Bottom Fan Issue 
The bottom fan is not operating within its normal parameters. 
Calculated Next Maintenance Month 
Calculated month of the next scheduled maintenance. Used in conjunction with 
[Calculated Next Maintenance Year]. 
Calculated Next Maintenance Year 
Calculated year of the next scheduled maintenance. Used in conjunction with 
[Calculated Next Maintenance Month]. 
Chilled Water Control Valve Failure 
Chilled water valve out of position. Chilled water control valve position does not 
match expected value. 
Clogged Air Filter 
Air filter is dirty and needs to be (cleaned or) replaced. 
Compressor 1 High Head Pressure 
Compressor 1 high head pressure. 
Compressor 1 High Pressure 
Transducer Issue 
Compressor 1 high pressure transducer is disconnected or the signal is out of 
range. 
Compressor 1 Hours Exceeded 
Operating hours for compressor 1 have exceeded the threshold. 
Compressor 1 Low Pressure Transducer 
Issue 
Compressor 1 low pressure transducer is disconnected or the signal is out of 
range. 
Compressor 1 Low Suction Pressure 
Compressor 1 low suction pressure. 
Compressor 1 Pump Down Issue 
Unable to pump down suction-side pressure during compressor 1 shutdown. 
Compressor 1 Short Cycle 
Compressor 1 short cycle. A short cycle is defined as turning on and off a 
number of times over a set time period. 
Condenser 1 Issue - Event Control 
Enable/disable the activation of the [Condenser 1 Issue] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list. 
Condenser 1 Issue - Event Type 
The event type for the [Condenser 1 Issue] event. 
Condenser 1 Issue 
Condenser 1 is not operating within its normal parameters. 
Condenser Circuit Unspecified General 
Event 
One or more unspecified condenser circuit events active. See local unit display 
for further details. 
Condenser Control Board Issue 
The condenser control board is reporting an issue. 
Condenser Fan Issue 
Condenser fan is not operating within its operational parameters. 
Condenser Fan Power 
Condenser fan's measured input power. 
Condenser Fan Speed 
Condenser fan speed expressed as a percentage of the maximum rated speed. 
Condenser Low Noise Mode - Full Days 
Days of the week selected for low noise mode full day scheduling. 
Condenser Low Noise Mode - Interval 
Days 
Days of the week selected for low noise mode interval scheduling. 
Condenser Low Noise Mode Max Fan 
Speed 
Maximum fan speed when condenser is placed in low noise mode. 
Condenser Low Noise Mode Schedule 
Control 
Enable/disable scheduled control of condenser low noise mode. 
Condenser Low Noise Mode Start Time 
The time of day at which the condenser will transition into low noise mode. 
Condenser Low Noise Mode State 
State of condenser low noise mode scheduler control.