Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
269
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Remote Sensor Temperature Calculation 
Calculation method applied to temperature readings from the remote sensors to 
determine a single temperature measurement value for cooling and heating 
control. 
Remote Sensor Temperature 
Air temperature as measured by remote sensor. 
Return Air Over Temp Threshold 
Threshold value used in the [Return Air Over Temperature] event. 
Return Air Over Temperature 
Return air high temperature event. 
Return Air Sensor Issue 
The air sensor at the inlet of the unit is disconnected or the signal is out of range. 
Return Air Temperature 
The temperature of the inlet air 
Return Dew Point 
Dew point temperature measured at the inlet of the unit. 
Return Humidity Out Of Proportional 
Band 
[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional 
Band], or has dropped below the lower limit of [Humidification Proportional Band] 
], for an extended period of time. 
Return Humidity 
Relative humidity measured at the inlet of the unit. 
Server Class 
The general classification for this system 
Service Required - Event Control 
Enable/disable the activation of the [Service Required] event. If set to 'disabled', 
the event will not be annunciated. This implies that the event will not be placed in 
any active event list or in any event history list. 
Service Required - Event Type 
The event type for the [Service Required] event. 
Service Required 
Unit requires servicing. 
Shutdown - Loss Of Power - Event 
Control 
Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list. 
Shutdown - Loss Of Power - Event Type 
The event type for the [Shutdown - Loss Of Power] event. 
Shutdown - Loss Of Power 
System lost power. This event becomes active when the unit is powered on 
following an unexpected loss of power. This event remains active for 90 minutes. 
Smoke Detected - Event Control 
Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', 
the event will not be annunciated. This implies that the event will not be placed in 
any active event list or in any event history list. 
Smoke Detected - Event Type 
The event type for the [Smoke Detected] event. 
Smoke Detected 
Smoke detected. 
Supply Air Over Temp Threshold 
Threshold value used in the [Supply Air Over Temperature] event. 
Supply Air Over Temperature 
Supply air high temperature event. 
Supply Air Sensor Issue 
The air sensor at the outlet of the unit is disconnected or the signal is out of 
range. 
Supply Air Temperature 
Air temperature measured at the outlet of the unit. 
Supply Air Under Temp Threshold 
Threshold value used in the [Supply Air Under Temperature] event. 
Supply Air Under Temperature 
Supply air low temperature event. 
Supply Chilled Water Loss of Flow 
Supply chilled water flow is too low. 
Supply Chilled Water Over Temp 
Threshold 
Threshold value used in the [Supply Chilled Water Over Temp] event. 
Supply Chilled Water Over Temp 
[Supply Chilled Water Temperature] has exceeded [Supply Chilled Water Over 
Temp Threshold]. 
Supply Chilled Water Temperature 
Supply chilled water temperature. 
Supply Fluid Temp Sensor Issue 
The supply fluid temperature sensor is disconnected or the signal is out of range. 
Supply Humidity 
Relative humidity at the outlet of the unit. 
System Control Mode 
System control mode. 
System Date and Time 
The system date and time 
System Event Acknowledge/Reset 
Reset and/or acknowledge all events. 
System On/Off Control 
Turn system functionality on or off. 
System Operating State Reason 
The reason the system is in the current operating state. 
Table 86
Liebert CRV
 - Glossary (continued)
Data Label
Data Description